Installation Guide

BIG ASS FAN 4900
WWW.BIGASSFANS.COM ©2013 DELTA T CORP. ALL RIGHTS RESERVED
6
Preparing the work site
Before beginning installation, review the mechanical and electrical installation guidelines below.
Mechanical installation
The fan weighs 150 lbs (60 kg). A suitable means for lifting the weight of the fan, such as a scissor lift, and at least two installation
personnel will be required.
• Big Ass )DQVFDQRQO\EHKXQJIURPDQ,EHDPRUDQJOHLURQV)RUVSHFL¿FUHTXLUHPHQWVVHHWKH0HFKDQLFDO,QVWDOODWLRQVHFWLRQ
in this guide. Do not mount the fan to single purlins, trusses, or bar joists. Consult a structural engineer for installation methods not
covered in this manual.
The mounting structure must be able to withstand the torque forces generated by the fan. The fan generates nearly
120 ft·lb (162.7 N·m) of torque during operation.
)DQVPRXQWHGRQIDEULFDWHG,EHDPVZKLFKDUHFRPPRQLQVWHHOEXLOGLQJVFRXOGFDXVHWKHEHDPWRÀH[DQGWKHIDQWRPRYH
VLJQL¿FDQWO\GXULQJRSHUDWLRQ,IWKLVÀH[LQJFDXVHVDFOHDUDQFHSUREOHP%LJAss Fans suggests contacting a structural engineer.
Adhere to the safety requirements in the table below when selecting the fan location.
Safety requirement Minimum distances
Clearance
IWIURPDOOIDQSDUWV7KHIDQLQVWDOODWLRQDUHDPXVWEHIUHHRIREVWUXFWLRQVVXFKDVOLJKWVFDEOHV
sprinklers, or other building structure. The fan should be at least 5 ft (1.5 m) from the ceiling.
Blade height IWDERYHWKHIORRU
+9$&HTXLSPHQW
[IDQGLDPHWHULIDWVDPHOHYHORUDERYHGLIIXVHU[IDQGLDPHWHULIEHORZGLIIXVHU5HIHUWRWKH
illustration below.
Fan spacing 2.5x fan diameter, center-to-center
Radiant/IR heaters See the manufacturer’s requirements for the minimum clearance to combustibles.
Electrical installation
7RUHGXFHWKHULVNRIHOHFWULFVKRFNZLULQJVKRXOGEHSHUIRUPHGE\DTXDOL¿HGHOHFWULFLDQ,QFRUUHFWDVVHPEO\FDQFDXVHHOHFWULF
VKRFNRUGDPDJHWKHPRWRUDQGWKHFRQWUROOHU
The installation of a Big Ass Fan must be in accordance with the National Electrical Code, ANSI/NFPA 70-2011, and all local codes.
Refer to the Electrical Installation section in this manual for detailed electrical requirements.
Controller output/motor input leads cannot share a conduit with any other controller’s AC supply feed.
Pre-Installation (cont.)
I-Beam Angle Iron
If the fan is mounted at the same level
or higher than the diffuser, the winglets
must be at a distance that is at least 1x
the measure of the fan’s diameter.
If the fan is mounted below the diffuser,
the winglets must be at a distance that
is at least 2x the measure of the fan’s
diameter.
[IDQ¶VGLDPHWHU
(14 ft)
(4.3 m)
+9$&
Diffuser
[IDQ¶VGLDPHWHU
(28 ft)
(8.5 m)
+9$&
Diffuser
14-ft diameter
14-ft diameter