Preparing the work site
Before beginning installation, review the mechanical and electrical installation guidelines below.
Mechanical installation
• The fan weighs 150 lbs (60 kg). A suitable means for lifting the weight of the fan, such as a scissor lift, and at least two installation
personnel will be required.
• Big Ass )DQVFDQRQO\EHKXQJIURPDQ,EHDPRUDQJOHLURQV)RUVSHFL¿FUHTXLUHPHQWVVHHWKH0HFKDQLFDO,QVWDOODWLRQVHFWLRQ
in this guide. Do not mount the fan to single purlins, trusses, or bar joists. Consult a structural engineer for installation methods not
covered in this manual.
• The mounting structure must be able to withstand the torque forces generated by the fan. The fan generates nearly
120 ft·lb (162.7 N·m) of torque during operation.
• )DQVPRXQWHGRQIDEULFDWHG,EHDPVZKLFKDUHFRPPRQLQVWHHOEXLOGLQJVFRXOGFDXVHWKHEHDPWRÀH[DQGWKHIDQWRPRYH
VLJQL¿FDQWO\GXULQJRSHUDWLRQ,IWKLVÀH[LQJFDXVHVDFOHDUDQFHSUREOHP%LJAss Fans suggests contacting a structural engineer.
• Adhere to the safety requirements in the table below when selecting the fan location.
Safety requirement Minimum distances
Clearance
IWIURPDOOIDQSDUWV7KHIDQLQVWDOODWLRQDUHDPXVWEHIUHHRIREVWUXFWLRQVVXFKDVOLJKWVFDEOHV
sprinklers, or other building structure. The fan should be at least 5 ft (1.5 m) from the ceiling.
Blade height IWDERYHWKHIORRU
+9$&HTXLSPHQW
[IDQGLDPHWHULIDWVDPHOHYHORUDERYHGLIIXVHU[IDQGLDPHWHULIEHORZGLIIXVHU5HIHUWRWKH
illustration below.
Fan spacing 2.5x fan diameter, center-to-center
Radiant/IR heaters See the manufacturer’s requirements for the minimum clearance to combustibles.
Electrical installation
• 7RUHGXFHWKHULVNRIHOHFWULFVKRFNZLULQJVKRXOGEHSHUIRUPHGE\DTXDOL¿HGHOHFWULFLDQ,QFRUUHFWDVVHPEO\FDQFDXVHHOHFWULF
VKRFNRUGDPDJHWKHPRWRUDQGWKHFRQWUROOHU
• The installation of a Big Ass Fan must be in accordance with the National Electrical Code, ANSI/NFPA 70-2011, and all local codes.
• Refer to the Electrical Installation section in this manual for detailed electrical requirements.
• Controller output/motor input leads cannot share a conduit with any other controller’s AC supply feed.
Pre-Installation (cont.)
I-Beam Angle Iron
If the fan is mounted at the same level
or higher than the diffuser, the winglets
must be at a distance that is at least 1x
the measure of the fan’s diameter.
If the fan is mounted below the diffuser,
the winglets must be at a distance that
is at least 2x the measure of the fan’s
diameter.
[IDQ¶VGLDPHWHU
(14 ft)
(4.3 m)
+9$&
Diffuser
[IDQ¶VGLDPHWHU
(28 ft)
(8.5 m)
+9$&
Diffuser
14-ft diameter
14-ft diameter