Installation Guide
31
WWW.BIGASSFANS.COM ©2013 DELTA T CORP. ALL RIGHTS RESERVED
BIG ASS FAN 4900
Fault messages (cont.)
Message Description
Incompatible EPM fault
Drive hardware error
Cycle power, and then reprogram EPM. If the fault will not clear, replace the drive and EPM.
External fault
Digital input programmed for this feature has been energized/de-energized depending on programming. P121-P124
EPM fault
EPM is missing or defective.
Replace the EPM.
to
Hardware Failure
Replace the drive.
4–20 mA Signal Loss
Check signal source and wiring, i.e., SmartSense365
™
wiring error.
OEM Defaults Data Fault
The OEM parameters in the EPM module do not match the anticipated defaults according to the VFD. This fault
may appear immediately upon VFD power-up.
To correct this conditionSUHVVWKH6723EXWWRQDQGWKHQSUHVVWKH0HPRU\(QWHUEXWWRQ8VHWKH83'2:1
button to scroll to P1993UHVVWKH0HPRU\(QWHUEXWWRQ8VHWKH83'2:1EXWWRQWRVFUROOWRDVHWWLQJRI0.
3UHVVWKH0HPRU\(QWHUEXWWRQWRVDYHWKHFKDQJH7KH9)'LVQRZDEOHWRUHDGZULWHWKH(30SURSHUO\
High Voltage fault
Check AC incoming power or increase fan deceleration time.
Low Voltage fault
Check AC incoming power
Output Transistor fault
Short circuit, excessive load, excessive cable charging current
9HULI\FRUUHFWORDGPRWRU+3PRWRUZLULQJFDEOHOHQJWKFDEOHW\SH
Motor Short to Ground
Motor Thermal OL
Check actual motor current against FLA (P108)
Flying Restart fault
Failed motor speed sync attempt
Single Phase fault
Incoming AC line phase loss
Check supply power.
Start fault
Start command was present on powerup.
Cycle start command.