WHERE TO INSTALL YOUR FAN
Before beginning installation, check that the building structure and fan location meet Big Ass Solutions’ safety
guidelines by confirming the below requirements.
Fans mounted on fabricated I-beams, which are common in steel buildings, could cause the beam to flex and
the fan to move significantly during operation. If this flexing causes a clearance problem, we suggest contacting
a structural engineer.
The fan must be installed so that it is plumb to the ground.
All fan parts must be ≥2 ft (61 cm) from all obstructions. The fan installation area must be free of obstructions
such as lights, cables, sprinklers, or other building structure components.
The fan must be installed so that it is ≥10 ft (3 m) above the finished floor.
Clearance guidelines
If a fan application does not meet these requirements, contact Customer Service to discuss alternative installations
or other fan options.
General clearance
Multiple fans must be spaced at a center-to-center distance that is no less than 2.5x the fan diameter.
The fan must be installed so that it is ≥10 ft (3 m) above the finished floor.
Ceiling clearance
The fan must be installed at least 5 ft (1.5 m) from the ceiling.