Instructions / Assembly
M
R F
RUN
STOP
AUTO FWD
REV
U
/T1
V/T2
W
/T3
PE
L1 L2 N
1 2 5 6 13A13B13C 14 30 16 1725 4 11
1 2 5 6 13A13B13C 14 30 16 1725 4 11
BLACK
GREEN/YELLOW
GREEN/YELLOW
AC Input Wiring
2W plus GND
Motor Output Wiring
3W plus GND
WHITE
BLACK
RED
WHITE
WWW.BIGASSFANS.COM © 2018 DELTA T LLC ALL RIGHTS RESERVED.
18
VFD WIRING DIAGRAMS
Note: Fire relay not shown in VFD wiring diagrams. See Wiring: Fire Relay for fire relay wiring instructions.
Wiring: 100–125 V, 1 Ф, 50/60 Hz
WARNING: Wait three minutes after disconnecting before servicing!
The diagram below shows wiring for a 100–125 V, 1 Φ, 50/60 Hz VFD. The VFD includes a pre-attached
10-ft (3-m) power supply cord. The L2 terminal is not used when wiring the VFD for 100–125 V, 1 Φ. This VFD
does not include a disconnect.