TROUBLESHOOTING
Review the troubleshooting tips listed below before contacting Customer Service for support.
Symptom
Solution
A popping noise is coming from
the fan.
Airfoil noise occurs when
airfoils are not tightened to the
specified torque.
Disconnect the fan from power, and then tighten the airfoil hardware
to 29 ft·lb (39.3 N·m). If popping still occurs, verify that the airfoils are
not contacting each other. If they are, contact Customer Service.
The fan will not start. Make sure all wires are securely connected and that supply power
is adequate and functional. If the fan still does not start, contact
Customer Service.
The VFD generates radio
frequency (RF) noise.
VFDs generate RF noise in many
ways, but this can be prevented
using proper wiring practices.
Do not run your fan and sensitive equipment on the same power
line.
Ensure proper grounding at the motor, at the VFD, and from the
VFD to the utility.
If noise is still present, contact Customer Service.
The motor makes noise when
fan speed is increased.
Audible high-frequency carrier noise may be an indicator of a stall
condition.
Some motor, gearbox, or VFD noise is to be expected and is
normal.
The fan wobbles during
operation.
Verify that the mounting structure is rigid enough to support the
fan and that the fan is not being exposed to external air forces.