Instructions / Assembly

AC Input Wiring
2W plus GND
Motor Output Wiring
3W plus GND
M
R F
RUN
STOP
AUTO FWD
REV
U
/T1
V/T2
W
/T3
PE
L1 L2 N
1 2 5 6 13A13B13C 14 30 16 1725 4 11
1 2 5 6 13A13B13C 14 30 16 1725 4 11
BLK
WHT
GRN/
YEL
BLK
RED GRN/
YEL
WHT
WWW.BIGASSSOLUTIONS.COM © 2015 DELTA T CORP. ALL RIGHTS RESERVED.
22
VFD Wiring: 100–125 V, 1 Ф
WARNING: Wait three minutes after disconnecting before servicing!
WARNING: Improper installation can cause electric shock or damage to the motor and controller. A
qualified electrician should perform the installation.
The diagram below shows wiring for a 100–125 V, 1 Ф, 50/60 Hz VFD. See the Technical Specifications section for
detailed power requirements. If multiple VFDs are connected to one feeder circuit, the circuit required is the sum
of the feeder circuit requirements listed in the chart. This type of installation will also require that each VFD be
installed downstream from a dedicated over-current protection device.
The VFD includes a pre-attached 10-ft (3 m) power supply cord. The L2 terminal is not used when wiring the VFD
for 100–125 V, 1 Φ. The VFD does not include a disconnect.
Note: The VFD does not contain fusing! Power must be supplied to the VFD via a dedicated circuit breaker or
properly fused disconnect!