User's Manual

Veri-Series Setup Guide
© Copyright 2005 Bioscrypt Inc. All rights reserved. Document #430-00111-18
14
Use one pair (e.g. blue/white and white/blue) for RS-485
connections. Connect readers identically at each reader (e.g.
blue/white on Cat5 to RS-485 (-) on pigtail/Weidmuller
Connector and white/blue on Cat5 to RS-485 (+) on
pigtail/Weidmuller Connector).
5. [RS-485 network only]: At converter, jumper TD(A) with RD(A)
and TD(B) with RD(B). Connect Blue/white from Cat5 to either
of A terminals and White/blue from Cat5 to either of B
terminals. Make certain to connect power correctly.
6. [RS-485 network only]: RS-485 supports distances up to 4,000
feet (1,200 meters) and/or 31 readers. To extend these
limitations, contact Bioscrypt Technical Support. Typically no
end-of-line termination is required unless the total run exceeds
2,000 feet.
RS-232
TD(A)
TD(B)
RD(A)
RD(B)
+12VDC
GND
RS-485 (-)
RS-485 (+)
Connect to
Earth
Ground
Twisted Pair.
Use Cat5 rated cable
Power
Supply
Unit Unit Unit Unit
3
Data0
Data1
Wiegand Gnd.
2
RS-232
/RS-485
Converter
Cat5
Twisted
Pair
Computer
Door
Controller