Use one pair (e.g. blue/white and white/blue) for RS-485 connections.
Connect readers identically at each reader (e.g. blue/white on Cat5 to RS-
485 (-) on pigtail/Weidmuller Connector and white/blue on Cat5 to RS-485
(+) on pigtail/Weidmuller Connector).
Power
Supply
Unit Unit Unit Unit
3
Data0
Data1
Wiegand Gnd.
2
RS-232
/RS-485
Converter
Cat5
Twisted
Pair
Computer
Door
Controller
5. [RS-485 network only]: At converter, jumper TD(A) with RD(A) and
TD(B) with RD(B). Connect Blue/white from Cat5 to either of A terminals
and White/blue from Cat5 to either of B terminals. Make certain to connect
power correctly.
RS-232
TD(A)
TD(B)
RD(A)
RD(B)
+12VDC
GND
Twisted Pair.
Use Cat5 rated cable
RS-485 (+)
RS-485 (-)
Connect to
Earth Ground
6. [RS-485 network only]: RS-485 supports distances up to 4,000 feet (1,200
meters) and/or 31 readers. To extend these limitations, contact Bioscrypt
Technical Support. Typically no end-of-line termination is required unless
the total run exceeds 2,000 feet.
7. [RS-485 network only]: Set up network using 9600 baud rate. Only
increase this data rate after the system is operating properly at 9600.