User's Manual

Page 24
Document #430-90003-08 © Copyright 2003, Bioscrypt Inc. All rights reserved.
Ethernet Network Topology
Communication cables for Ethernet logically form a straight line bus, however, the
more devices placed on that bus, the less efficient the network due to increased
collisions and the weaker the signal will get due to increased distance. Repeaters
can be used to boost signal strength, however a better solution would be placing
switches at intermediate positions along the bus. The most common Ethernet
topology in use today is the star configuration (see figure 11), with a hub or switch
in the center.
RS-485 Cable Termination
Most RS-485 buses require termination because of fast transitions, high data rates,
or long cables. The purpose of the termination is to prevent adverse transmission-
line phenomena, such as reflections.
For example, suppose an installation uses 2000 feet of cable. A round trip, then,
covers 4000 feet. Using a propagation velocity of 0.66c (two thirds the speed of
light – contact the cable supplier for this value for your cable), one round trip is
completed in approximately 6.2 micro-seconds. If we assume the reflections will
damp out in three round trips up and down the cable length, the signal will
stabilize 18.6 micro-seconds after the leading edge of a bit. At 56 k-baud (57,600
bits per second) one bit is 17.4 micro-seconds wide. In this case, the reflections do
not damp out before more information is being sent, and corruption of
information is a potential problem. Termination will solve this problem as will
lowering the baud rate. At 9600 baud, the bit width is 104 micro-seconds wide,
the reflections are damped out much before the center of the bit, and
termination is not required. Longer cable length and higher baud rates each push
the case for use of termination.
A common mistake is to connect a terminating resistor at each node - a practice
that causes trouble on buses that have four or more nodes. The active driver sees
the four termination resistors in parallel, a condition that excessively loads the
driver. If each of the four nodes connects a 100 termination resistor across the
bus, the active driver sees a load of 25 instead of the intended 50. The problem
becomes substantially worse with 32 nodes. If each node includes a 100
termination resistor, the load becomes 3.12.