This function is used to set the size of the SMD field:
1.
Set the “additional fall-delay time” function (section 4.5) to
its lowest value (F + 1 + 1).
2. Set the SMD function (section 4.7) to its highest level
(F + 3 + 9).
3. Go into the detection area (to trigger detection) and remain
in front of the door where you wish the SMD field to be. In
doing so pay attention to the green LED.
a)
If the green LED goes out immediately, you have not
been detected by the SMD field. Increase the set
level by 1 in order to increase the SMD field. Repeat
point 3 until the desired SMD field size has been
determined and set.
b) If the green LED remains lit, you have been detected
by the SMD field. Decrease the set level by 1 in order
to decrease the size of the SMD field. Repeat point 3
until the desired SMD field size has been determined
and set.
4.
Reset the “additional fall-delay time” (section 4.5) and the
“SMD” (section 4.7) functions to their previous values.
Consider that the position of the SMD field is influenced by
the inclination angle and the swivel angle of the radar mod-
ule (see sections 6.1 and 6.2).
+ +
(levels 1 to 9)
71 9F
4.8 Field size SMD
These pre-programmed settings are designed for quick and
easy configuration in the case of standard applications.
Functions of the motion detector and presence detector are
set during this process. General functions and settings of the
interface signals are not changed.
+ = standard door
+ = pavement
+ = retirement home
Remote control unit can only read back and display comfort
functions correctly if all the parameters still correspond to
the preprogrammed values. If individual functions are adjusted,
only key lights up on the remote control unit.
The pre-programmed values of the enhanced functions are
shown in the enhanced functions” overview table on page 24.
C
3C
2C
1C
4.2 Comfort functions
When direction recognition is switched on, only motion in
the direction of the sensor is detected. When direction
recognition is switched off, all motion is detected.
Direction recognition Direction recognition
ON OFF
4.3 Direction recognition
+ + =
ON
+ + =
OFF
8 1F
8 2F
+
(levels 1 to 9)
See page 38 for field dimensions of the motion detector.
4.4 Field size (sensitivity)
D 1 9
Jupiter SE (escape routes): According to the direc-
tive Automatic sliding doors on escape routes”,
the field depth must be at least 1.5 m.
Door remains Door opens with
closed with frontal or side
cross-traffic movements
Delayed drop-out of the output signal is dependent on the
settings of several functions. The additional fall-delay time
only begins after other delaying functions have completed
their cycle.
4.5 Additional output fall-delay time
+ +
(levels 1 to 6)
11 6F
For cross-traffic optimisation, the optimum inclination angle
of the radar is 30° to 45° (see also section 6.1).
We recommend that the cross-traffic optimisation facility be
used without the clip (see also section 6.3).
4.6 Cross-traffic optimisation
+ + =
OFF
+ +
(levels 2 to 9)
51F
529F
The additional SMD field is activated after detection is made;
it makes it possible to monitor a person who remains in the
door area. The SMD function recognises the slightest move-
ments, thus providing a marked increase in convenience in
the extended door area. In addition to the SMD sensitivity,
the size of the SMD area can be adjusted to 9 different
levels (see section 4.8).
4.7 Slow motion detection (SMD)
SMD field
Detection area
++
=
OFF
++
…=
decreasing sensitivity
++
…=
constant sensitivity
963F
523F
13F
Additional
SMD field
+ = wide door
+ = narrow door
5C
4C