19.4 Troubleshooting
Red LED
Regular flashing
pattern
Regular flashing
pattern
Regular flashing
pattern
1. Disconnect device from supply voltage
2. Restart device
3. Wait for “Switching on and initialising” to flash
4. Check whether setting and masked out lens segments match in
accordance with chapter 10.7
5. If not, correct and restart (points 1–3)
6. If regular flashing pattern reoccurs
Continue with optical unit error 2
1. Disconnect device from supply voltage
2. Remove all possible external covers in front of and underneath
the sensor
3. Carefully clean optical unit window on inside and outside
4. Put on protective cover and restart device
5. Wait for “Switching on and initialising” to flash
6. Wait a further 3 min.
7. If regular flashing pattern reoccurs
Continue with optical unit error 3
1. Disconnect device from supply voltage
2. Reduce inclination angle of presence detector (slightly closer to
door)
chapter 12.1
3. Put on protective cover and restart device
4. Wait for “Switching on and initialising” to flash
5. Wait a further 3 min.
6. If regular flashing pattern reoccurs
Reduce mounting height to max. 3 m
or
Switch OFF floor self-test of presence detector (see chapter 18)
or
Renew unit
1. Disconnect device from supply voltage
2. Remove all possible external covers in front of and underneath
the sensor
3. Restart device
4. Wait for “Switching on and initialising” to flash
5. Wait a further 30 s
6. If regular flashing pattern reoccurs
Switch OFF module self-test of motion detector (see chapter 18)
or
Remove any fluorescent tubes in vicinity (e.g. emergency exit lights)
or
Renew unit
Display
Remedy / troubleshooting
Green LED
Regular
flashing
pattern
Possible cause
Optical unit error 1:
Width of detection
area
Optical unit error 2:
Optical unit dirty
or covered
Optical unit error 3:
Max. mounting
height (3 m)
exceeded
Module self-test
motion detector
Error messages are displayed by the two display elements (green and red LEDs). This text describes the possible causes and
corresponding troubleshooting measures.
Function overview (remote control unit)
The Reglobeam is operated via a combination of function and
numerical keys. Flashing keys on the Reglobeam mean that
data transfer was incomplete. The infrared interface should not
be exposed to direct sunlight and other light sources.
The Reglobeam remote control unit allows you to programme the
Jupiter/Jupiter SE/Jupiter Presence easily and conveniently from
floor level. Data transfer between the Reglobeam and the sensor
takes place in both directions, i.e. to and from the sensor; it is
ensured by an infrared interface. The set values are read back
by the Reglobeam immediately after programming, and are
displayed so that they can be checked. This provides for safe and
correct programming.
20
Function
Reglobeam remote control unit