Installation manual
10
Set-up Mode U
In the set-up function, it is possible to set the oven controller to match the mechanical set-up and the choice
of software.
If the set-up has been changed in U1, U4 or U15, the oven will be reset.
U1 Oven model
You select the oven model (B, C or
K) by pressing the step key. 1= K, 2= C, 3= B.
You press the temperature key to select a Pass-Through model (two doors).
1= one door (standard) 2= two doors
When you have selected the oven model, confirm by pressing the alarm key if the control lamp flashes.
After that, the
controller initialises. NOTE: ALL settings and programs are reset.
U2 Oven size
You choose the oven size by pressing the step key: 0-7.0= 1.06, 1= 1.08, 2= 1.10, 3= 1.12, 4= 1.16, 5= 1.20,
6= 2.10, 7= 2.14. The oven size you have chosen is shown in the field next to the
temperature key.
U3 CombiClean
You activate or deactivate CombiClean by pressing the step key. 0=OFF, 1=ON.
U4 Temperature scale
You choose between Celsius and Fahrenheit as scale of temperature by pressing the step key.
0= Celsius 1= Fahrenheit.
You can ”even out” the current temperature by pressing the temperature key.
0=OFF, 1=ON When
you have chosen the temperature scale, confirm by pressing the alarm key if the
control lamp flashes. After that, the controller initialises. NOTE: ALL settings and programs are reset.
U5 Not in use
U6 Low-temperature steaming
You activate and deactivate low-temperature steaming by pressing the step key.
0= OFF, steaming only possible at
212°F (100°C), 1= ON, steaming only possible between 86°F (30°C) and
248°
F (120°C).
NOTE: This function is available on K models only. If chosen on a B or C model, nothing happens.
U7 Preheating at 572°F (300°C)
You activate and deactivate preheating by pressing the step key. 0= OFF, 1= ON.
NOTE: Preheating at temperatures above 484 °F (250°C) is only possible for max. 15 minutes.
U8 Setting water level sensor
When you press the temperature key, the water level value starts flashing and can then be set between 40
and 80 (default 70). If the conductivity of the water is low, set the water level higher.
U9 Automatic restart
You activate and deactivate automatic restart by
pressing the step key.
0= OFF, 1= 10 minutes, 2= 30 minutes, 3= 60 minutes. This means that if there is a power cut, the program
that was interrupted will be resumed provided that the power returns within the time set.
U10 Programs
You activate the program mode by pressing the step
key. 0= OFF, 1= 10 programs with 3 process steps.
NOTE: It is still possible to activate the cleaning program even though the program mode is active.
0= OFF.
U11 Core temperature probe
You activate and deactivate the core temperature probe by pressing the step key. 0= OFF, 1= ON.
U12 Drain cooling
You activate and deactivate drain cooling by pressing the step key. 0= OFF, 1= ON.
U13 Timer start
You activate or deactivate timer start by pressing the step key. 0= OFF, 1= ON.