Technical data
BKI 09 ATEX 0003X
htk4014a0600p_01.doc
37 / 80
Minimum 100 mm
Maximum 24 000 mm
1.1.6 Probe length
Ordered length + 100mm
Set probe length + 100mm.
This value should be modified when the probe has been replaced or shortened
(cable probes).
The output unit is set via Fct. 1.2.4 Length Unit.
With an empty tank, using the function F11
nt he “Dynamic Configuration” menu
an automatic search for the probe tip
can be carried out to update the parameter.
The value determines simultaneously:
- the minimum value of the tank height, Fct. 1.1.1
- the maximum setting range for the dead zone,
Fct. 1.1.2.
Probe length may be set greater than tank height but less than 24 000 mm for
special installations.