Technical data
BKI 09 ATEX 0003X
htk4014a0600p_01.doc
39 / 80
Function Input Range Description
1.3.0 Current output
Select Off, Level, Distance, Volume* or
Ullage volume*
1.3.1 Current 1 item
Level
Selection of the required function for the current output.
Select 4-20mA or
4-20mA + 22 mA on error.
1.3.2 Current 1 range
4 – 20mA
This parameter defines the status which the current output assumes nt he
event of a fault:
4-20 mA (last measured value held nt he event of a fault)
4-20 mA / E = 22 mA (is set to 22 mA nt he event of a fault).
Enter a value from 0 mm** to a value lower
than that entered for Fct. 1.3.4
Scale I max.
1.3.3 Scale I1 min.
As per order
This function defines the lower limit
of the analog measuring range.
It is 4 mA.
The value of this parameter always has to be lower than the value selected for
Fct. 1.3.4: Scale I1 max..
Enter value higher than the value selected
under Fct. 1.3.3. “Scale I min.” up to tank
height or the maximum volume table
value***
1.3.4 Scale I1 max.
As per order
This function defines the upper limit of the analog measuring range.
It is 20 mA.
The value of this parameter must always be:
- lower than or equal to the value selected under Fct. 1.1.1:
Tank height or the maximum volume table value,
- higher than the value selected under Fct. 1.3.3:
Scale I1 min., otherwise an error message will appear during parameter
check.
Select No delay, 10 sec., 20 sec., 30 sec.,
1 min., 2 min., 5 min. or 15 min.
1.3.5 Error delay
No delay
This menu is only available when (4-20 mA / E = 22 mA)
has been selected under Fct. 1.3.2: Current 1 range.
With this parameter, a time delay can be defined for transition of the current
output to 22 mA after an error has been noted.
During the delay, measurement and the analog output are held.
When the error disappears, the delay also serves to return to the measuring
mode.
complete Fct. 1.7.2 “Input table” before selecting “volume“ or “ullage volume”
** or other unit selected in Fct. 1.2.4 Length Unit, 1.2.5 Volume Unit depending nt he item selected in Fct. 1.3.1 Current 1 Item.
*** depends on value selected in Fct. 1.3.1 Current 1 Item