Technical data
BKI 09 ATEX 0003X 
 htk4014a0600p_01.doc 
 41 / 80 
Function  Input Range  Description 
1.5.0 Application 
1.5.1. Detection delay 
Minimum value:  0mm 
Maximum value: Dead Zone 
As per order 
This function can be used to define an area directly below the flange in which 
interference reflections (e.g. from the tank nozzle) are masked. This value has 
to be smaller than or equal to the dead zone (Fct. 1.1.2.). 
1.6.0 Serial I/O 
  For integrating into a signal network. 
Standard hardware platform for HART® is the current loop with superposed 
FSK signals. 
For a multidrop application the current output is set to “OFF” and consequently 
to a constant 4 mA. With a multidrop bus, up to 15 HART® devices can be 
operated. 
Addresses from 0 to 15 1.6.2  Address 
0 
With this function, every device connected to a bus is assigned an address 
between 0 and 15 (HART® protocol). 
If several devices are connected to a digital bus, each device must be assigned 
a unique address under which it can then be identified in the bus. 
0 = Analogue output active 
1 - 15 = Multi-drop mode active, 
 analogue output inactive 
1.7.0 Volume table    For calibrating the gauge for volume measurement. 
Select point 01 to 20, enter level and then 
volume values respectively. 
1.7.2. Input table 
0 
(conversion table not created, volume 
measurement not possible) 
This function is used for setting up the strapping table (level/volume). Up to 20 
points can be assigned. Every new point must be larger than the preceding one. 
The units of length and volume can be changed later without affecting the 
settings in the table. 
The units selected for length and volume in fct.s 1.2.4 and 1.2.5 will be used 
here. 










