Technical data
44 / 80 
 BKI 09 ATEX 0003X 
 htk4014a0600p_01.doc 
Example procedure 1 (using PCSTAR 2): 
to change true tank height (10000mm or 33 ft) to factory configured probe length, L
2 
(9000mm or 29½ ft) , and 
then save the new parameter. Refer to item 5 in the diagram above. 
Step  Action  Data entered / value set 
1  Press F2 to connect to the device  Tank status screen displayed (level reads 6750 mm) 
2  Press F2 to enter configuration menu  Configuration menu displayed 
3  Click on the data set field for Fct. 1.1.1 Tank height  This field currently reads 10000 (mm) 
4  Type in the new value  9000 
5  Press the button “F6-Send to MicroTrek” for the MicroTREK 2-wire to 
immediately accept the new value. 
n/a 
6  Press “F3-Exit” to quit the configuration menu.  Tank status screen displayed (level now reads 5750 mm) 










