Technical data

44 / 80
BKI 09 ATEX 0003X
htk4014a0600p_01.doc
Example procedure 1 (using PCSTAR 2):
to change true tank height (10000mm or 33 ft) to factory configured probe length, L
2
(9000mm or 29½ ft) , and
then save the new parameter. Refer to item 5 in the diagram above.
Step Action Data entered / value set
1 Press F2 to connect to the device Tank status screen displayed (level reads 6750 mm)
2 Press F2 to enter configuration menu Configuration menu displayed
3 Click on the data set field for Fct. 1.1.1 Tank height This field currently reads 10000 (mm)
4 Type in the new value 9000
5 Press the button “F6-Send to MicroTrek” for the MicroTREK 2-wire to
immediately accept the new value.
n/a
6 Press “F3-Exit” to quit the configuration menu. Tank status screen displayed (level now reads 5750 mm)