Technical data
48 / 80
BKI 09 ATEX 0003X
htk4014a0600p_01.doc
Supplementary procedure for setting the 4 … 20 mA current to output volume readings (using PCSTAR 2)
Step Action Data entered/value selected
1 Go to user function 1.3.1 ”Current 1 item” to select measurement function. Volume
2 Go to user function 1.3.2 ”Current 1 range” to set fault status 4 … 20 mA
3 Go to user function 1.3.3 “Scale I1 min” to enter volume value for the minimum output (4 mA) 0.50 m³
4 Go to user function 1.3.3 “Scale I1 max” to enter volume value for the maximum output (20 mA) 16.80 m³
5 Either save the new configuration to disk by left-clicking on
F5-Save to disk and download it onto the MicroTREK 2-wire using the F6-Send to MicroTrek key.
n/a
6 Press F3 to exit the configuration menu. n/a