Technical data
BKI 03 ATEX 027X spa3804a0600p_06
17 / 44
P02: - c b a Calculation units FACTORY DEFAULT: 000
a Temperature
0 °C
1 °F
This table is interpreted according to P00(c), P01(a) and P02(c) and is irrelevant in case of percentage measurement [ P01(a)= 2 or 4 )]
Volume Weight (set also P32) Volume flow
b
Metric US Metric US Metric US
0 m
3
ft
3
- lb (pound) m
3
/time ft
3
/time
1 litre gallon tons tonnes litre/time gallon/time
c Time
0 s
1 min
2 hour
3 day
Attention!
EasyTREK is a level transmitter. Although it can be used for
measuring weight, due to factors involved in doing so, accuracy
may essentially be influenced.
P04 - - - - Maximum Distance to be Measured (H) FACTORY DEFAULT: X
M
as per chart
This is the only parameter that has to be programmed for each application other than distance (however to avoid disturbing effect of
possible multiple echoes it is suggested to do this in distance measurement applications too).
The maximum distance to be measured is the greatest distance between the surface of the transducer and the farthest level to be measured.
The factory programmed, greatest distances (DEFAULT values) which can be measured by the units are listed in the table below. For the actual
application the maximum distance to be measured i.e. the distance between the sensor and the bottom of the tank should be entered in P04.
Maximum measuring distance X
M
m/feet
EasyTREK
Level transmitter for liquids
Transducer material PP / PVDF Transducer material PTFE
SP_-39 4/13
3/10
SP_-38 6/20
5//16
SP_-37 8/26
6/20
SP_-36 10/33
-
SP_-34 15/49
-
Since the level is determined by calculating the difference between the value set in P04 and distance (DIST) is measured by the unit, it is
essential that the correct value of (H) is set in P04. To obtain the best accuracy it is suggested that this distance is measured in the empty tank.