Technical data

BKI 03 ATEX 027X spa3804a0600p_06
21 / 44
5.3.3. RELAY OUTPUT
P13: - - - a Relay function
a Relay function Also set:
0 DIFFERENTIAL LEVEL CONTROL
(Hysteresis control)
Relay is energised if the measured or
calculated value exceeds the value set in P14
Relay is de-energised if the measured or
calculated value descends under the value set
in P15
Relay
Level
P14
P15
Time
Energised:
De-energised:
P14, P15
There is a need to set (in level
min 20mm) hysteresis between
P14 and P15
P14 > P15 – normal operation
P14 < P15 – inverted operation
1 Relay is energised in case of Echo Loss -
2 Relay is de-energised in case of Echo Loss -
3 COUNTER
Used for open channel flow metering.
A 140 msec pulse is generated every 1, 10,
100, 1.000 or 10.000 m
3
according to P16.
P16= 0: 1m
3
P16= 1: 10 m
3
P16= 2: 100 m
3
P16= 3: 1.000 m
3
P16= 4: 10.000 m
3
In de-energised state of the device the „C1” circuit is closed.
FACTORY DEFAULT: 2
P14: … Relay parameter – Operating value FACTORY DEFAULT: 0
P15: … Relay parameter – Releasing value FACTORY DEFAULT: 0
P16: … Relay parameter – Pulse rate FACTORY DEFAULT: 0
FACTORY DEFAULTS: P14=0, P15=0, P16=0
C2 C1
C2 C1