Technical data
BKI 03 ATEX 027X  spa3804a0600p_06
 29 / 44
P37: yyyy Real-time clock, year
Year setting for date of the on-board clock. (2005)
P38: mmdd Real-time clock, month and day
Month (mm) and day (dd) setting for date of the on-board clock.
P39: HHMM Real-time clock, hour and minute
 Hour (HH) and minute (MM) setting of the on-board clock.
5.3.6.1 READING DATA OUT FROM THE LOGGER
Reading the logger is only possible with digital communication. For this purpose the built-in IrDA communication port can be used. The content of the
log can also be read out via HART communication, but because of the slow speed of HART, it takes several hours. To access the data content use
of NIVELCO’s DataScope program is recommended. During this high-speed communication the device sets the output current to
22 mA. There is no measurement while retrieving data from the register, so measurement values are not updated.
Connecting to a PC using an IrDA adapter:
The IrDA adapter and the IrDA port of the device must be placed whithin
a 5…50 cm distance and facing each other!
Recommended IrDA adapters:
(only IrDA to RS232 adapters can be used)*
- RedSnake:
- ActiSys:
- Esis:
IL-200
ACT-IR200S
ACT-IR220L+
ACT-IR220LR
M8421
* Recommended RS232-USB adapters for using the USB port: STLab: USB-RS232
MOXA: NPort-U1110, UPort 1110
After connecting the adapters start DataScope program. The program and the User’s Manual can be found on the EviewLight CD.