Server User Manual

Logging Enabled
Log interval 600 second
Number of power outlets 4 (depends on the type/model of the RPC)
# config -s config.ports.port2.power.type=APC 7900
# config -s config.ports.port2.power.name=MyRPC
# config -s "config.ports.port2.power.description=RPC in room 5"
# config -s config.ports.port2.power.username=rpclogin
# config -s config.ports.port2.power.password=secret
# config -s config.ports.port2.power.snmp.community=v1
# config -s config.ports.port2.power.log.enabled=on
# config -s config.ports.port2.power.log.interval=600
# config -s config.ports.port2.power.outlets=4
The following five commands are used by the Management Console to add the RPC to “Managed
Devices”:
# config -s config.devices.device3.connections.connection1.name=myRPC
# config -s "config.devices.device3.connections.connection1.type=RPC Unit"
# config -s config.devices.device3.name=myRPC
# config -s "config.devices.device3.description=RPC in room 5"
# config -s config.devices.total=3
The following command will synchronize the live system with the new configuration:
# config -a
14.11 Environmental
To configure an environmental monitor with the following details:
Monitor name Envi4
Monitor Description Monitor in room 5
Temperature offset 2
Humidity offset 5
Enable alarm 1 ? yes
Alarm 1 label door alarm
Enable alarm 2 ? yes
Alarm 2 label window alarm
Logging enabled ? yes
Log interval 120 seconds
# config -s config.ports.port3.enviro.name=Envi4
# config -s "config.ports.port3.enviro.description=Monitor in room 5"
# config -s config.ports.port3.enviro.offsets.temp=2
# config -s config.ports.port3.enviro.offsets.humid=5
# config -s config.ports.port3.enviro.alarms.alarm1.alarmstate=on
# config -s config.ports.port3.enviro.alarms.alarm1.label=door alarm
# config -s config.ports.port3.enviro.alarms.alarm2.alarmstate=on
# config -s config.ports.port3.enviro.alarms.alarm2.label=window alarm
# config -s config.ports.port3.enviro.alarms.total=2
# config -s config.ports.port3.enviro.log.enabled=on
# config -s config.ports.port3.enviro.log.interval=120
Assign alarms.total=2 even if they are off.
The following 5 commands will add the environmental monitor to “Managed devices”: