Then connect the drain pipe to the sewage system using the Siphon-Kit SFK 20x32 (available upon separate order). The pipes are
required to have a minimum slope of 3°. Each drain pipe is connected to a different U-trap.
min 3°
Drain hose
U-trap
Sewage system
Drain pipe
The condensate drainage system is designed for normal operation in premises with air temperatures above 0 °C! If the expected ambient
air temperatures are below 0 °C, the condensate drainage system must be equipped with heat insulation and pre-heating facilities.
Condensate drainage is not required for the KOMFORT (EC) D5(B)180-E units as they are equipped with an enthalpy heat exchanger.
www.blaubergventilatoren.de
KOMFOrt (EC) d5(B)180(-E)
14