Datasheet

Toroidal transformer
RKD
General Data
Rated input voltage 2 x 115 Vac
Rated output voltage 2 x 12 - 2 x 115 Vac
Power 15 - 3000 VA
Insulation class B
Maximum ambient temperature 40 °C
Efficiency up to 98 %
Degree of protection IP 00
Advantages
Minimum size at high output
Low weight
Double input voltage for series or parallel connection
Double output voltage for series or parallel connection
Minimal no-load losses
Outstanding temperature behaviour thanks to low magnetic leakage field
Very low noise field
Applications
As a mains transformer for adjustment of the voltage and simple electrical
isolation.
As an isolating transformer for the safe electrical isolation of the input and
output sides. The transformer may be used to set up protective separation as
a protective measure in accordance with VDE 0100.
As a safety isolating transformer for the safe electrical isolation of the input
and output sides. The transformer is suitable for creating SELV and PELV
circuits because of the limit on the output voltage.
Standards / 2 "
Certifications W
Mains transformer
to: VDE 0570 Teil 2-1, DIN EN 61558-2-1, EN 61558-2-1, IEC 61558-2-1, UL
5085-1/-2, CSA 22.2 No.66
Isolating transformer
to: VDE 0570 Part 2-4, DIN EN 61558-2-4, EN 61558-2-4, IEC 61558-2-4,
UL 5085-1/-2, CSA 22.2 No.66
Safety isolating transformer
to: VDE 0570 Part 2-6, DIN EN 61558-2-6, EN 61558-2-6, IEC 61558-2-6,
UL 5085-1/-2, CSA 22.2 No.66
UL 5085-1/-2, CSA 22.2 No.66
Toroidal transformer
RKD
Type RKD 15/.. RKD 20/.. RKD 30/.. RKD 40/..
Input
Rated input Voltage 2 x 115 Vac 2 x 115 Vac 2 x 115 Vac 2 x 115 Vac
Rated frequency 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
Output
Rated output voltage: Order no.
2x12 Vac: RKD 15/2x12
2x15 Vac: RKD 15/2x15
2x18 Vac: RKD 15/2x18
2x12 Vac: RKD 20/2x12
2x15 Vac: RKD 20/2x15
2x18 Vac: RKD 20/2x18
2x24 Vac: RKD 20/2x24**
2x12 Vac: RKD 30/2x12
2x15 Vac: RKD 30/2x15
2x18 Vac: RKD 30/2x18
2x24 Vac: RKD 30/2x24*
2x12 Vac: RKD 40/2x12
2x15 Vac: RKD 40/2x15
2x18 Vac: RKD 40/2x18
2x24 Vac: RKD 40/2x24*
Rated Power 15 VA 20 VA 30 VA 40 VA
No-load voltage (app. x factor) 1.15 1.30 1.16 1.18
No-load loss (typ.) 0.30 W 0.20 W 0.45 W 0.40 W
Efficiency 83 % 74 % 82 % 84 %
Standards
Classification
Safety isolating transformer Safety isolating transformer
**Mains transformer
Safety isolating transformer
*Isolating transformer
Safety isolating transformer
*Isolating transformer
Approvals
Approvals cURus cURus cURus cURus
Environment
Ambient temperature max. 40 °C 40 °C 40 °C 40 °C
Safety and protection
Type
open type open type open type open type
Class of Insulation System
VDE=B, UL=class 105 VDE=B, UL=class 105 VDE=B, UL=class 105 VDE=B, UL=class 105
Protection index
IP 00 IP 00 IP 00 IP 00
Safety class (prepared)
II II II II
Short circuit strength
non-short-circuit proof non-short-circuit proof non-short-circuit proof non-short-circuit proof
Test voltage 4000 Vac, 50 Hz 4000 Vac, 50 Hz 4000 Vac, 50 Hz 4000 Vac, 50 Hz
Order numbers
Order Number refer to rated output voltage refer to rated output voltage refer to rated output voltage refer to rated output voltage
+
-
TRANSFORMERS
146
Subject to change

Summary of content (8 pages)