Setting Input Thresholds
Settings for each channel’s high and low thresholds are provided. The connected relay’s normal operating state will toggle (change state) if these thresh-
olds are met. For both high and low thresholds, the activation and deactivation levels are different to prevent the relay from rapidly toggling (cycling on
and off). Each channel has Hi ON and Hi OFF settings and Lo ON and Lo OFF settings.
Relay Setup Screen with Relay Normally = Off (Open)
Relay Setup Screen with Relay Normally = On (Closed)
Example. If the relay is Normally On (closed) and Bilge 1 is congured as above, then it will open when the bilge has been running longer than 10
minutes in any given hour. When the runtime drops below 8 minutes/hr then the relay will turn off again.
To change one of the settings, scroll to desired setting and press Select. Press the LEFT or RIGHT arrow buttons to change the value and
then press Enter to save the setting. Press Cancel to cancel the change.
NOTE: Lower threshold settings cannot be set above higher threshold settings. Similarly, higher thresholds cannot be set below lower thresholds.
The monitor will automatically increase or decrease the thresholds to enforce this.
LEGEND
Bilge Run Time
10 min
8 min
Time
ONOFF
RELAY NORMALLY OFF
Bilge Hi On
Bilge Low Off
10 min
8 min
Time
ONOFF
RELAY NORMALLY ON
Bilge Hi On
Bilge Low Off