Reference Manual Part 2

Technical Reference Manual - TransPondIT for CENTRON Electric Meter
31
Tilt Switch Activated
[16]
Is the meter fitted
upside down?
Follow utility procedures for
removing and re-
fitting meter in the
correct orientation. Report findings
Using ConFigIT clear the status code and
check that TransPondIT is coun
ting correctly.
Refer to chapters 3 & 5
END
Is there any
obvious
physical
damage?
Report finding to
appropriate utility
personnel
Call RAMAR
Technical
Support
1-888-987-2627
YES
NO
NO
YES
YES
NO
Figure C-4: Tilt switch
Confirm correct operation of the meter.
(i.e. Meter reading increments. LCD
reading and radio reading are as set
by configuration). Note: If the LCD is