BA16 16 SEER SPLIT SYSTEM AIR CONDITIONER PRODUCT SPECIFICATIONS FORM NO.
16 SEER SPLIT SYSTEM AIR CONDITIONER BA16 PHYSICAL AND ELECTRICAL DATA Model Compressor Max. Overcurrent Rated Locked Device Load Rotor (amps) (amps) (amps) Volts/Hz/Phase Voltage Range Min. Circuit Amp. 208-230/60/1 197-253 12.4 20 9.4 208-230/60/1 197-253 15.0 25 208-230/60/1 197-253 17.0 208-230/60/1 197-253 208-230/60/1 Outdoor Fan Motor Refrig. Charge (oz.) Shipping Weight (lbs.) 1075 77 150 1/6 825 86 160 1.0 1/6 825 100 180 83 1.0 1/6 825 102 185 16.
14 SEER SPLIT SYSTEM AIR CONDITIONER BA16 UNIT DIMENSIONS & SOUND RATINGS Dimensions (inch) Model BA16L18P BA16LR18P BA16L24P BA16LR24P BA16L30P BA16LR30P BA16L36P BA16LR36P BA16L41P BA16L42P BA16LR42P Sound A - Width B - Depth C - Height Rating (dBA) 24.25 24.25 29 71 28.25 28.25 29 76 28.25 28.25 37 74 28.25 28.25 37 74 28.25 28.25 37 76 28.25 28.25 33 76 BA16L47P 28.25 28.25 37 80 BA16L48P 28.25 28.25 33 80 BA16L59P 32.25 32.25 37 78 BA16L60P 32.25 32.
16 SEER SPLIT SYSTEM AIR CONDITIONER BA16 BA16L60P-1 BA16L48P-1 Suction Liquid Suction Liquid Suction Liquid Piston(2) BC1P43(B,C)+TDR 14.5 12.2 34000 25500 1200 7/8 3/8 7/8 3/8 7/8 3/8 0.071 BC4X43(B,C)+45 SEC BLOWER DELAY 14.5 12.2 34000 25500 1200 7/8 3/8 7/8 3/8 7/8 3/8 0.071 Evap. Coil(3) Rated Sensible BTUH BC4X49C+TDR 14.5 12.2 34000 25500 1200 7/8 3/8 7/8 3/8 7/8 3/8 0.071 BC4X48(B,C)+45 SEC BLOWER DELAY 14.5 12.
14 SEER SPLIT SYSTEM AIR CONDITIONER BA16 COOLING PERFORMANCE WITH EVAPORATOR COILS AC'S Note: 1 Certified in accordance with Unitary Air Conditioner Certification Program, which is based on AHRI Standard 210/240 2 Required to achieve AHRI rating. If NA (Not Applicable) is in the piston column, then TXV is required. 3 A blower time delay relay is required to achieve AHRI rating. This feature is standard on all Allied Air Enterprises furnace and AH products.
16 SEER SPLIT SYSTEM AIR CONDITIONER BA16 Evap Coil Furnace Model BCE3M24E****4X AHRI Rated Capacity BTUH Sensible Capacity CFM 16 13 18000 13000 650 BCE3M24V****4X 16 13 18000 13000 650 BCE3M18V****4X 14.5 12.
14 SEER SPLIT SYSTEM AIR CONDITIONER BA16 BA16L18P-1 Furnace Model BC4X23B 95G2UH045BV12 BC4X23B 95G2UH070BV12 Evap Coil EER Indoor Model SEER Outdoor Unit COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES AHRI Rated Capacity BTUH Sensible Capacity CFM 16 13 18000 13000 650 16 13 18000 13000 650 BC4X23B EFV08BC 16 13 18000 13000 650 BC4X24A 80G2UH070AV12 16 13 18000 13000 650 BC4X24B 80G2UH090BV16 16 13 18000 13000 620 BC4X24B 95G2UH070BV12 16 13 18000 130
16 SEER SPLIT SYSTEM AIR CONDITIONER BA16 EER Indoor Model SEER BA16L18P-1 Outdoor Unit COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES AHRI Rated Capacity BTUH Sensible Capacity CFM 15.1 13 18000 13000 650 15.1 13 18000 13000 620 15.1 13 18000 13000 650 EFV08BC 15.1 13 18000 13000 650 BC1P30B 80G1UH070BE12 15.1 13 18000 13000 620 BC1P30B 95G1UH045BE12 15.1 13 18000 13000 620 BC1P30B 95G1UH070BE12 15.1 13 18000 13000 650 BC1P30B 95G2UH045BE12 15.
14 SEER SPLIT SYSTEM AIR CONDITIONER BA16 BA16L18P-1 AHRI Rated Capacity BTUH Sensible Capacity CFM 15.1 13 18000 13000 650 14.5 12.2 18000 13000 650 14.5 12.2 18000 13000 650 95G1UH070BE12 14.5 12.2 18000 13000 650 95G2UH070BE12 Furnace Model EFV08BC BC1P24B 95G1UH070BE12 BC1P24B 95G2UH070BE12 BC4X24B BC4X24B Evap Coil BC4X36B BA16L24P-1 EER Indoor Model SEER Outdoor Unit COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES 14.5 12.
16 SEER SPLIT SYSTEM AIR CONDITIONER BA16 BA16L24P-1 Furnace Model BC4X23A 80G1UH045AE12 Evap Coil EER Indoor Model SEER Outdoor Unit COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES AHRI Rated Capacity BTUH Sensible Capacity CFM 16 13 23000 17000 850 BC4X23A A80US2V070A12L 16 13 23000 17000 850 BC4X23B 95G1UH045BE12 16 13 23000 17000 785 BC4X23B 95G1UH070BE12 16 13 23000 17000 835 BC4X23B 95G2UH045BV12 16 13 23000 17000 850 BC4X23B 95G2UH070BE12 16 13 230
14 SEER SPLIT SYSTEM AIR CONDITIONER BA16 BA16L24P-1 EER Indoor Model SEER Outdoor Unit COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES AHRI Rated Capacity BTUH Sensible Capacity CFM 15.1 13 23000 17000 760 15.1 13 23000 17000 850 15.1 13 23000 17000 800 95G2UH070BV12 15.1 13 23000 17000 850 BC1P29B EFV08BC 15.1 12.5 23000 17000 850 BC1P30A 80G1UH045AE12 15.1 12.
16 SEER SPLIT SYSTEM AIR CONDITIONER BA16 EER Indoor Model SEER Outdoor Unit COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES AHRI Rated Capacity BTUH Sensible Capacity CFM 15.1 13 23000 17000 850 15.1 13 23000 17000 820 15.1 13 23000 17000 800 95G2UH045BV12 15.1 13 23000 17000 850 EFV08BC 15.1 13 23000 17000 850 ED1P24A+H4TXV01 80G1DF045AE12 15 12.5 23000 17000 835 ED1P24B+H4TXV01 80G1DF070BE12 15 12.
14 SEER SPLIT SYSTEM AIR CONDITIONER BA16 Evap Coil Furnace Model BCE3M30E****4X BCE3M30C****P BA16L30P-1 BC1P36B 80G2UH090BV16 EER Indoor Model SEER Outdoor Unit COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES AHRI Rated Capacity BTUH 15.1 13 28000 21000 1000 14 12.
16 SEER SPLIT SYSTEM AIR CONDITIONER BA16 BA16L30P-1 Furnace Model BC1P36A 80G1UH045AE12 Evap Coil EER Indoor Model SEER Outdoor Unit COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES AHRI Rated Capacity BTUH Sensible Capacity CFM 15.1 13 28000 21000 1000 BC1P36A 80G2UH070AV12 15.1 13 28000 21000 1000 BC1P36B 80G1UH070BE12 15.1 13 28000 21000 1000 BC1P36B 80G1UH090BE16 15.1 13 28000 21000 1000 BC1P36B 95G1UH045BE12 15.
14 SEER SPLIT SYSTEM AIR CONDITIONER BA16 BA16L36P-1 EER Indoor Model SEER BA16L30P-1 Outdoor Unit COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES AHRI Rated Capacity BTUH Sensible Capacity CFM 14.5 12.2 28000 21000 1000 14.5 12.2 28000 21000 1000 14.5 12.2 28000 21000 1000 BCE3M36C****P 14 12.2 34000 25500 1200 BCE3M36E****4X 14 12.
SEER SPLIT SYSTEM AIR CONDITIONER BA16 BA16L36P-1 EER Indoor Model SEER Outdoor Unit COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES AHRI Rated Capacity BTUH Sensible Capacity CFM 15.5 12.5 34000 25500 1155 12.5 34000 25500 1155 Furnace Model BC4X43C 95G1UH090CE16 BC4X43C 95G2UH090CE16 15.5 Evap Coil BC1P36A 80G2UH070AV12 15.1 13 34000 25500 1200 BC1P36B 80G1UH090BE16 15.1 12.5 34000 25500 1180 BC1P36B 95G2UH045BV12 15.
14 SEER SPLIT SYSTEM AIR CONDITIONER BA16 SEER EER Indoor Model AHRI Rated Capacity BTUH Sensible Capacity CFM 15.1 12.5 34000 25500 1200 13 34000 25500 1200 15 12.5 34000 25500 1215 15 12.5 34000 25500 1215 95G1UH045BE12 15 12.5 34000 25500 1215 95G2UH045BE12 15 12.5 34000 25500 1215 15 12.5 34000 25500 1215 Furnace Model BC4X43C 80G1UH090CE20 BC4X43C EFV16CC 15.
16 SEER SPLIT SYSTEM AIR CONDITIONER BA16 EER Evap Coil Furnace Model SEER Indoor Model AHRI Rated Capacity BTUH Sensible Capacity BA16L36P-1 Outdoor Unit COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES Note: 1 Certified in accordance with Unitary Air Conditioner Certification Program, which is based on AHRI Standard 210/240 2 Required to achieve AHRI rating. If NA (Not Applicable) is in the piston column, then TXV is required 3 A blower time delay relay is required to achieve AHRI rating.
14 SEER SPLIT SYSTEM AIR CONDITIONER BA16 Evap Coil Furnace Model EER Indoor Model SEER Outdoor Unit COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES AHRI Rated Capacity BTUH Sensible Capacity Note: 1 Certified in accordance with Unitary Air Conditioner Certification Program, which is based on AHRI Standard 210/240 2 Required to achieve AHRI rating. If NA (Not Applicable) is in the piston column, then TXV is required 3 A blower time delay relay is required to achieve AHRI rating.
16 SEER SPLIT SYSTEM AIR CONDITIONER BA16 EER Indoor Model SEER Outdoor Unit COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES AHRI Rated Capacity BTUH BCE3M42E****4X 14.5 12.2 40000 30000 1400 BCE3M42C****P+H4TXV02 14 12.2 40000 30000 1400 14 12.
14 SEER SPLIT SYSTEM AIR CONDITIONER BA16 EER Indoor Model SEER BA16L42P-1 Outdoor Unit COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES AHRI Rated Capacity BTUH Sensible Capacity CFM 14.5 12.2 41000 30000 1400 12.2 41000 30000 1400 14.5 12.2 41000 30000 1400 14.5 12.2 41000 30000 1400 Furnace Model BC1P49C+H4TXV02 95G1UH110CE20 BC1P49C+H4TXV02 95G2UH110CE20 14.5 BC1P62C+H4TXV02 95G1UH110CE20 BC1P62C+H4TXV02 EFV16CC Evap Coil BC4X49C 95G1UH110CE20 14.5 12.
16 SEER SPLIT SYSTEM AIR CONDITIONER BA16 EER Indoor Model SEER BA16L48P-1 Outdoor Unit COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES AHRI Rated Capacity BTUH BCE3M48E****4X 15.1 12.5 46500 34500 1600 BCE3M48V****4X 14.5 11.7 47000 34500 1600 BCE3M48C****P+H4TXV02 14 12 46500 34500 1600 Evap Coil Furnace Model Sensible Capacity CFM BC1P62C+H4TXV02 80G1UH090CE20 15.1 12.5 46500 34500 1545 BC1P62C+H4TXV02 80G1UH110CE20 15.
14 SEER SPLIT SYSTEM AIR CONDITIONER BA16 Evap Coil BA16L48P-1 BC1P60D+H4TXV02 Furnace Model 95G2UH135DV20 EER Indoor Model SEER Outdoor Unit COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES AHRI Rated Capacity BTUH Sensible Capacity CFM 14.5 12 46000 34500 1600 BC1P62C+H4TXV02 80G2UH110CV20 14.5 12 46500 34500 1600 BC1P62C+H4TXV02 95G2UH090CE16 14.5 11.7 46500 34500 1600 BC1P62C+TXV 95G2UH090CE16 14.5 12.5 46500 34500 1560 BC1P62D+H4TXV02 80G1UH135DE20 14.
16 SEER SPLIT SYSTEM AIR CONDITIONER BA16 EER Indoor Model SEER BA16L60P-1 Outdoor Unit COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES AHRI Rated Capacity BTUH BCE3M60C****P+H4TXV03 14 12 58000 42000 1800 BCE3M60V****4X 14 12 58000 42000 1780 Evap Coil Furnace Model Sensible Capacity CFM ED1P50/60C+H4TXV03 80G1DF110CE20 14 11.7 57000 42000 1800 ED1P50/60C+H4TXV03 95G1DF110CE20 14 11.7 57000 42000 1800 ED1P50/60C+H4TXV03 95G2DF110CE20 14 11.
14 SEER SPLIT SYSTEM AIR CONDITIONER BA16 COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES Note: 1 Certified in accordance with Unitary Air Conditioner Certification Program, which is based on AHRI Standard 210/240 2 Required to achieve AHRI rating. If NA (Not Applicable) is in the piston column, then TXV is required 3 A blower time delay relay is required to achieve AHRI rating. This feature is standard on all Allied Air Enterprises furnace and AH products.
16 SEER SPLIT SYSTEM AIR CONDITIONER BA16 COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES Note: 1 Certified in accordance with Unitary Air Conditioner Certification Program, which is based on AHRI Standard 210/240 2 Required to achieve AHRI rating. If NA (Not Applicable) is in the piston column, then TXV is required 3 A blower time delay relay is required to achieve AHRI rating. This feature is standard on all Allied Air Enterprises furnace and AH products.
14 SEER SPLIT SYSTEM AIR CONDITIONER BA16 COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES Note: 1 Certified in accordance with Unitary Air Conditioner Certification Program, which is based on AHRI Standard 210/240 2 Required to achieve AHRI rating. If NA (Not Applicable) is in the piston column, then TXV is required 3 A blower time delay relay is required to achieve AHRI rating. This feature is standard on all Allied Air Enterprises furnace and AH products.
16 SEER SPLIT SYSTEM AIR CONDITIONER BA16 COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES Note: 1 Certified in accordance with Unitary Air Conditioner Certification Program, which is based on AHRI Standard 210/240 2 Required to achieve AHRI rating. If NA (Not Applicable) is in the piston column, then TXV is required 3 A blower time delay relay is required to achieve AHRI rating. This feature is standard on all Allied Air Enterprises furnace and AH products.
14 SEER SPLIT SYSTEM AIR CONDITIONER BA16 COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES Note: 1 Certified in accordance with Unitary Air Conditioner Certification Program, which is based on AHRI Standard 210/240 2 Required to achieve AHRI rating. If NA (Not Applicable) is in the piston column, then TXV is required 3 A blower time delay relay is required to achieve AHRI rating. This feature is standard on all Allied Air Enterprises furnace and AH products.
16 SEER SPLIT SYSTEM AIR CONDITIONER BA16 COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES Note: 1 Certified in accordance with Unitary Air Conditioner Certification Program, which is based on AHRI Standard 210/240 2 Required to achieve AHRI rating. If NA (Not Applicable) is in the piston column, then TXV is required 3 A blower time delay relay is required to achieve AHRI rating. This feature is standard on all Allied Air Enterprises furnace and AH products.
14 SEER SPLIT SYSTEM AIR CONDITIONER BA16 COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES Note: 1 Certified in accordance with Unitary Air Conditioner Certification Program, which is based on AHRI Standard 210/240 2 Required to achieve AHRI rating. If NA (Not Applicable) is in the piston column, then TXV is required 3 A blower time delay relay is required to achieve AHRI rating. This feature is standard on all Allied Air Enterprises furnace and AH products.
16 SEER SPLIT SYSTEM AIR CONDITIONER BA16 COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES Note: 1 Certified in accordance with Unitary Air Conditioner Certification Program, which is based on AHRI Standard 210/240 2 Required to achieve AHRI rating. If NA (Not Applicable) is in the piston column, then TXV is required 3 A blower time delay relay is required to achieve AHRI rating. This feature is standard on all Allied Air Enterprises furnace and AH products.
14 SEER SPLIT SYSTEM AIR CONDITIONER BA16 COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES Note: 1 Certified in accordance with Unitary Air Conditioner Certification Program, which is based on AHRI Standard 210/240 2 Required to achieve AHRI rating. If NA (Not Applicable) is in the piston column, then TXV is required 3 A blower time delay relay is required to achieve AHRI rating. This feature is standard on all Allied Air Enterprises furnace and AH products.
16 SEER SPLIT SYSTEM AIR CONDITIONER BA16 COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES Note: 1 Certified in accordance with Unitary Air Conditioner Certification Program, which is based on AHRI Standard 210/240 2 Required to achieve AHRI rating. If NA (Not Applicable) is in the piston column, then TXV is required 3 A blower time delay relay is required to achieve AHRI rating. This feature is standard on all Allied Air Enterprises furnace and AH products.
14 SEER SPLIT SYSTEM AIR CONDITIONER BA16 COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES Note: 1 Certified in accordance with Unitary Air Conditioner Certification Program, which is based on AHRI Standard 210/240 2 Required to achieve AHRI rating. If NA (Not Applicable) is in the piston column, then TXV is required 3 A blower time delay relay is required to achieve AHRI rating. This feature is standard on all Allied Air Enterprises furnace and AH products.
16 SEER SPLIT SYSTEM AIR CONDITIONER BA16 COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES Note: 1 Certified in accordance with Unitary Air Conditioner Certification Program, which is based on AHRI Standard 210/240 2 Required to achieve AHRI rating. If NA (Not Applicable) is in the piston column, then TXV is required 3 A blower time delay relay is required to achieve AHRI rating. This feature is standard on all Allied Air Enterprises furnace and AH products.
16 SEER SPLIT SYSTEM AIR CONDITIONER BA16 COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES Note: 1 Certified in accordance with Unitary Air Conditioner Certification Program, which is based on AHRI Standard 210/240 2 Required to achieve AHRI rating. If NA (Not Applicable) is in the piston column, then TXV is required 3 A blower time delay relay is required to achieve AHRI rating. This feature is standard on all Allied Air Enterprises furnace and AH products.
14 SEER SPLIT SYSTEM AIR CONDITIONER BA16 COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES Note: 1 Certified in accordance with Unitary Air Conditioner Certification Program, which is based on AHRI Standard 210/240 2 Required to achieve AHRI rating. If NA (Not Applicable) is in the piston column, then TXV is required 3 A blower time delay relay is required to achieve AHRI rating. This feature is standard on all Allied Air Enterprises furnace and AH products.
16 SEER SPLIT SYSTEM AIR CONDITIONER BA16 COOLING PERFORMANCE WITH EXTENDED RATINGS BA16L30P BA16L60P BC1P23 BC1P62C BC1P62C BA16L48P BC1P62C BC1P62C BA16L42P BC1P49C BC1P49C BA16L36P BC1P29 BA16L24P BC1P29 BA16L18P BC1P36B Outdoor Model Indoor Model Indoor Outdoor Temperature - DB ºF Temp DB/ 65º WB ºF Btuh 82º 95º S/T kW Btuh S/T kW Btuh S/T 105º 115º kW Btuh S/T kW Btuh S/T kW 85/72 24,600 0.61 1.24 23,500 0.63 1.47 22,600 0.64 1.65 20,800 0.68 1.
14 SEER SPLIT SYSTEM AIR CONDITIONER BA16 ACCESSORIES Description Where Used Kit Number Crankcase Heater All models 93M04 18 10J42 24, 30, 36, 41, 42, 47, 48, 59, 60 88M91 Low Ambient Kit All models 34M72 Short Cycle Protector All models 47J27 Hard Start Kit Freezestat Time Delay Relay Loss of Charge Kit Sound Blanket TXV Kit 3/8 tubing 93G35 5/8 tubing 50A93 All models 58M81 All models 84M23 (factory installed) 18, 24, 30, 36, 41 14W00 (factory Installed) 42, 47, 48, 59, 60
14 SEER SPLIT SYSTEM AIR CONDITIONER 4AC14 1-800-865-5931 All specifications and illustrations subject to change without notice and without incurring obligations. FORM NO. BA16-100 (12/2017) Printed in the U.S.A.