BE5C Specifications Sheet

ENHANCED AIR HANDLER
BE5C
Page 2
MODEL NUMBER GUIDE
METERING DE
VICE
4X = R410A TXV
1P = PISTON
VOLTAGE
A = 208/230V - 1 PHASE - 60HZ
POSITION
M = MULTI-POSITION
TONNAGE
18, 24, 30, 36, 42, 48, 60
PRODUCT
BC= BLOWER COIL
FEATURE SET
E = ENHANCED FEATURES
SERIES
5 = 5 SERIES (1 PIECE PLATFORM,
OMNIGUARD
TM
)
MOTOR & CONTROL
C = PSC
E = CONSTANT TORQUE
V = VARIABLE SPEED
BC E 5 C 18 M A 1P
PHYSICAL
INSTALLATION CLEARANCES WITH ELECTRIC HEAT
Model Volts/Hz/Phase
Max. Elec. Heat
Available (kW)
Transformer Size
& Type
Filter Size
(in.)
Refrigerant Connection (IDS)
Weight
(lbs.)
Suction (in.) Liquid (in.)
BE5C18
208-230/60/1 7.5 40 VA Class 2 15X20 3/4 3/8 109
BE5C24
208-230/60/1 10 40 VA Class 2 15X20 3/4 3/8 127
BE5C30
208-230/60/1 15 40 VA Class 2 15X20 3/4 3/8 133
BE5C36
208-230/60/1 15 40 VA Class 2 18X20 7/ 8 3/8 163
BE5C42
208-230/60/1 15 40 VA Class 2 18x20 7/ 8 3/8 168
BE5C48
208-230/60/1 20 40 VA Class 2 18x20 7/ 8 3/8 186
BE5C60
208-230/60/1 20 40 VA Class 2 18x20 7/ 8 3/8 186
Cabinet 0 in. (0 mm)
To Plenum 0 in. (0mm)
To Outlet Duct within 3 ft. (914mm) 0 in. (0 mm)
Floor 0 in. (0 mm) See Note #1
Service / Maintenance See Note #2
1 Units installed on combustible floors in the downflow position with electric heat require optional downflow combustible flooring base.
2 Front service access - 24 in. (610 mm) minimum.
Note - If cabinet depth is more than 24 in. (610mm), allow a minimum of the cabinet depth plus 2 in. (51 mm).