BE5C Specifications Sheet

ENHANCED AIR HANDLER
BE5C
Page 4
ELECTRICAL
1. For 208 volt use .751 correction factor for kW and Btuh
2. 12.5kW, 15 and 20kW (2 stage models) require 2 supply circuits
3. Circuit #1 includes blower motor amps except 20kW models
Model
Heating Capacity (240V)
Blower
Amps
Min. Circuit Ampacity
Max. Circuit Breaker
Size
Single Point Power Supply
Nominal
Heater
SizekW
kW Btuh
208V 240V 208V 240V 208V 240V
1 2 1 2 1 2 1 2 Amps Fuse Amps Fuse
BE5C18
0 0 0
1.1
5 5 15 15
5 4.8 16400 23 26 25 30
7.5 7.5 25600 35 40 35 40
10 9.6 32700 45 51 45 60
BE5C24
0 0 0
1.6
5 5 15 15
5 4.8 16400 24 27 25 30
7.5 7.5 25600 36 41 40 45
10 9.6 32700 45 52 45 60
BE5C30
0 0 0
2.2
5.0 5 15 15
5 4.8 16400 24 28 25 30
7.5 7.5 25600 37 42 40 45
10 9.6 32700 46 53 50 60
12.5 12.5 42600 40 19 46 22 40 20 50 25 59 60 68 70
15 14.4 49100 46 22 53 25 50 25 60 25 68 70 78 80
BE5C36
0 0 0
2
5 5 15 15
5 4.8 16400 24 28 25 30
7.5 7.5 25600 36 42 40 45
10 9.6 32700 46 53 50 60
12.5 12.5 42600 40 19 46 50 40 20 50 25 59 60 68 70
15 14.4 49100 46 22 53 25 50 25 60 25 68 70 78 80
BE5C42
0 0 0
2.5
5.0 5.0 15 15
5 4.8 16400 25 28 25 30
7.5 7.5 25600 37 42 40 45
10 9.6 32700 46 53 50 60
12.5 12.5 42600 41 19 47 22 45 20 50 25 60 60 68 70
15 14.4 49100 46 22 53 25 50 25 60 25 68 70 78 80
BE5C48
0 0 0
7.6
9.5 9.5 15 15
5 4.8 16400 31 35 35 35
7.5 7.5 25600 43 49 45 50
10 9.6 32700 53 60 60 60
12.5 12.5 42600 47 19 53 22 50 20 60 25 66 70 75 80
15 14.4 49100 53 22 60 25 60 25 60 25 75 80 85 90
20 19.2 65500 53 43 60 50 60 45 60 50 96 100 110 110
BE5C60
0 0 0
7.6
9.5 9.5 15 15
5 4.8 16400 31 35 35 35
7.5 7.5 25600 43 49 45 50
10 9.6 32700 53 60 60 60
12.5 12.5 42600 47 19 53 22 50 20 60 25 66 70 75 80
15 14.4 49100 53 22 60 25 60 25
60 25 75 80 85 90
20 19.2 65500 53 43 60 50 60 45 60 50 96 100 110 110