BE5C Specifications Sheet

ENHANCED AIR HANDLER
BE5C
Page 5
BLOWER
Model
Motor
Size (hp)
Blower
Size (in.)
Speed Tap
CFM @ ESP - in. W.C.
0.1 0.2 0.3 0.4 0.5
BE5C18
1/5 9X6
Low (Red) 540 525 505 470 420
Med (Blue) 690 670 640 605 550
High (Black) 920 880 855 790 710
BE5C24
1/3 9X6
Low (Red) 675 675 655 630 590
Med (Blue) 1010 980 940 805 740
High (Black) 1105 1045 1000 915 855
BE5C30
1/2 10X8
Low (Red) 870 870 855 810 770
Med (Blue) 1080 1055 1025 985 935
High (Black) 1310 1260 1255 1155 1085
BE5C36
1/3 10X8
Low (Red) 1020 970 955 910 805
Med (Blue) 1275 1240 1190 1150 1085
High (Black) 1560 1520 1445 1395 1325
BE5C42
1/2 10X8
Low (Red) 1300 1275 1250 1210 1155
Med (Blue) 1525 1495 1450 1390 1345
High (Black) 1815 1755 1695 1605 1530
BE5C48
1 12X10
Low (Red) 1250 1210 1185 1130 1110
Med-Low 1500 1465 1435 1400 1360
Med (Blue) 1715 1670 1635 1615 1575
Med-High 1770 1735 1700 1670 1650
High (Black) 1895 1860 1835 1795 1760
BE5C60
1 12X10
Low (Red) 1100 1050 1000 925 830
Med-Low 1625 1595 1565 1520 1490
Med (Blue) 1815 1785 1760 1730 1685
Med-High 1905 1870 1835 1810 1765
High (Black) 1980 1955 1925 1895 1860
All data given while air handler is operating with a wet DX coil and air filter installed.
Speeds marked in italics with an asterisk* are the factory settings for both heating and cooling. Cooling speeds should not be reduced below factory settings.
Dierent speeds can be set for heating mode.