Multizone Outdoor Unit Installation Manual

Revised 5/14/2020
NOTE: Be sure to maintain minimum clearanc-
es for optimum operation as shown below.
NOTE: Heat insulating tape should be used
on the drain joint to prevent freezing in colder
climates.
Drain Joint Installation (optional)
M
N
P
” from back wall
” on right
above
” on left
78” in front
Note: Drain joint will require additional clearance beneath the unit.
Condensation drains under the unit without installing the drain joint.
Outdoor Unit
Installation
Page 10
1. Fit the rubber seal on the end of the drain joint
that will connect to the outdoor unit.
2. Insert the drain joint into the hole in the bas
pan of the unit.
3. Rotate the drain joint 90° until it clicks in place
facing the front of the unit.
4. Connect a drain hose extension (not included
to the drain joint to redirect water from the
unit during heating mode.
If the drain joint doesn’t come with a rubber seal
(see Fig. 6 .9 - B ), do the following:
1. Insert the drain joint into the hole in the bas
pan of the unit. The drain joint will click in
place.
2. Connect a drain hose extension (not included)
to the drain joint to redirect water from the
unit during heating mode.
You must drill a hole in the wall for the refriger-
ant piping, and the signal cable that will connect
the indoor and outdoor units.
1. Determine the location of the wall hole based
on the location of the outdoor unit.
2. Using a 2.5” hole bit, drill a hole in the wall.
3. Place the protective wall cu in the hole. This
protects the edges of the hole and helps seal
it when you nish the installation process.
The 24K indoor unit can only be connected with
a 36k or 48k condenser due to refrigerant pipe
diameter. Use connection A on the 36k and
connections A&B on the 48k. (See Fig. 6.10)
Fig 6.8
Fig 6.9
Fig 6.10
Seal
Drain joint
(A) (B)
Base pan hole of
outdoor unit
Seal
Notes On Drilling Hole In Wall
Note: 24K Indoor Units Only
NOTE: When drilling the wall hole, make sure
to avoid wires, plumbing, and other sensitive
components.
Table 6.3: Refrigerant line size multizone
air handlers (unit: inch)
Indoor Unit capacity
(Btu/h)
Liquid Gas
9K 1/4" 3/8"
12K/18K 1/4" 1/2"
24K 3/8" 5/8"