U-Match Single Zone Installation Manual

1. Remove the test cover and fill 2000ml water in.
2. Turn on t
he A/C in cooling mode, check if there is
condensate water out.
3. Stop t
he A/C and wait for 3 minutes, then restart it to
check if there is a problem.
4. Continue to f
ill water inside to the max level, check if the
water pump start to work immediately.
5. Disconnect th
e drain pump and wait till the water level to
alarm level to see if there is a full-water-alarm and if the
A/C is shut down automatically.
Drain plug is for draining
all the water out when
there is a problem with
the A/C unit. Make sure it
is fixed well when the test
is carried out.
Drainage Test