Ceiling Cassette Air Handler Installation Manual

CAUTION
DO NOT mix anything other than the specied refrigerant, such as air, etc., inside the refrigerant
circuit.
Execute heat insulation work completely on both sides of the gas piping and liquid piping.
Otherwise, this can sometimes result in water leakage. (When using a heat pump, the
temperature of the gas piping can reach up to approximately 248° F. Use insulation which is
suciently resistant.)
Also, in cases where the temperature and humidity of the refrigerant piping sections might
exceed 86° F or Rh80%, reinforce the refrigerant insulation (3/4" or thicker). Condensation may
form on the surface of the insulating material.
Before rigging tubes, check which type of refrigerant is used.
Use a pipe cutter and are suitable for used refrigerant.
Only use annealed material for are connections.
If the refrigerant gas leaks during the work, ventilate the area. A toxic gas is emitted by the
refrigerant gas being exposed to a re.
Make sure there is no refrigerant gas leak. A toxic gas may be released by the refrigerant gas
leaking indoor and being exposed to ames from an area heater, cooking stove, etc.
Refer to the Fig 5.1 for the dimensions of are nuts spaces and the appropriate tightening
torque. (Over-tightening may damage the are and cause leaks.)
Check whether the height drop between the indoor unit and outdoor unit, and the length of
refrigerant pipe meet the following requirements in Fig 5.2:
The type of models Capacity
(Btu/h)
Max.allowable
piping length
Max.allowable
piping height
R410A inverter 12K 82ft 32.8ft
Split type air conditioner 18K 98.4ft 65.6ft
Fig 5.2
Fig 5.1
Pipe
gauge
Flaring
torque
Flare dimension
(A) (Unit: Inch)
Flare shape
Min. Max.
1/4" 14 ft/ lbs 0.33 0.34
3/8" 18 ft/ lbs 0.52 0.53
1/2" 26 ft/ lbs 0.64 0.65
5/8" 34 ft/ lbs 0.76 0.78
R0.4~0.8
45
°
±
2
90
°
±
4
A
Page 12
Revised 5/14/2020
5
Refrigerant Piping Installation
WARNING
All eld piping must be provided by a licensed refrigeration technician and must comply with the
relevant local and national codes
Refrigerant Piping
Installation