Ceiling Cassette Air Handler Installation Manual

6.1 Installation of drain piping
Install the drain piping as shown in gure below
and take measures against condensation.
Use PVC pipe, use of plastic, exible piping is
discouraged.
6.3 How to perform piping
Connect the drain hose to drain lift pipes, and
insulate them.
Connect the drain hose to the drain outlet on
the indoor unit, and tighten it with the clamp.
6.2 Install the drain pipes
Keep piping as short as possible and slope it
downwards at a gradient of at least 1/100 so
that air may not remain trapped inside the
pipe.
Keep pipe size equal to or greater than that of
the discharge pipe of the unit.
Push the drain hose as far as possible over
the drain socket, and tighten the metal clamp
securely.
Insulate the drain hose inside the building.
If the drain hose cannot be suciently set on
a slope, t the hose with drain lift piping (eld
supply).
Make sure that heat insulation work is
executed on the Indoor drain pipe and the
drain socket to prevent condensation.
3~5ft
Hanging bar
1/100 gradien
t
Fig 6.1
12
34
1 - Drain socket (attached to the unit)
2 - Metal clamp
3 - Drain hose
4 - Insulation (field supply)
Fig 6.3
5
11.8in
8.7in
29.5in
0~3in
20.9in
3~5ft
Ceiling Slab
Hanger
bracket
Adjustable
range
Drain
raising pipe
Metal
clamp
Drain
hose
Page 14
Revised 5/14/2020
6
Connecting The Drain Pipe
Connecting
The Drain Pipe