Hyper Heat Multizone Installation Manual

Page 28
Automatic
Correction Function
Automatic Wiring/Piping Correction Function
Function of Automatic Wiring/Piping Correction
11
More recent models now feature automatic correction of wiring/piping errors. Press the "check
switch" on the outdoor unit PCB board for 5 seconds until the LED displays "CE”, indicatomg that
this function is working, Approximately 5-10 minutes after the switch is pressed, the "CE" disappears,
meaning that the wiring/piping error is corrected and all wiring/piping is properly connected.
How To Activate This Function
1. Check that outside temperature is above 5.
(This function does not work when outside temperature is not above 5)
2. Check that the stop valves of the liquid pipe and gas pipe are open.
3. Turn on the breaker and wait at least 2 minutes.
4. Press the check switch on the outdoor PCB board unit LED display "C E".
Correct
Terminal
block