Multizone Wall Mounted Air Handler Installation Manual

6
Refrigerant Piping Connection
Note on Pipe Length
Maximum Length and Drop Height of Refrigerant Piping per Unit Model
Connection Instructions – Refrigerant Piping
The length of refrigerant piping will aect the performance and energy eciency of the unit. Nominal
eciency is tested on units with a pipe length of 16.5ft. In North America, standard pipe length is 25’.
A minimum pipe run of 10 feet is required to minimize vibration & excessive noise. Refer to the table
below for specications on the maximum length and drop height of piping.
Step 1: Cut pipes
When preparing refrigerant pipes, take extra care to cut and are them properly. This will ensure
ecient operation and minimize the need for future maintenance.
1. Measure the distance between the indoor and outdoor units.
Refrigerant Piping
Connection
Page 20
Revised 5/14/2020
Model
Max Length Max Drop Height
Add'l Refrigerant
9k & 12k 82 feet 33 feet 0.16/ foot
18k 99 feet 66 feet 0.16/ foot
24k 164 feet 82 feet 0.32/ foot