Step six: neaten the pipes
1. The pipes should be placed along the wall,
bent reasonably and hidden possibly. Min.
semidiameter of bending the pipe is 10cm.
2. If the outdoor unit is higher than the wall
hole, you must set a U-shaped curve in the
pipe before pipe goes into the room, in
order to prevent rain from getting into the
room.
Installation of outdoor unit
2. Fix the power connection wire and signal control wire with wire clip (only for
cooling and heating unit).
Note:
Never cut the power connection wire to prolong or shorten the distance.
U-shaped curve
wall
drain hose
Outdoor Condensate Drainage
During heating operation, the condensate and defrosting
water should be drained out reliably through the drain hose.
Install the outdoor drain connector in a Φ25 hole on
the base plate and attach the drain hose to the connector
so that the waste water formed in the outdoor unit can be
drained out. The hole diameter 25 must be plugged.
(The figures in this manual may be different with the material
objects, please refer to the material objects for reference)
The 09K ACD UNIT12K AFC UNIT24K AFE UNIT drainage
hole consists of two Φ25 and two kidney holes (see the fig.1).
The drain plug consists of one Φ25 and two kidney plugs.
Whether to plug other holes will be determined by the dealers
to actual conditions.
24K AFE UNIT:
Didney holes Drain - water hole
Bottom frame
Fig.1
09K ACD UNIT12K AFC UNIT:
Drain-water hole
Bottom frame
Didney holes
Didney holes
Drain plug
Hose (available commercially,
inner dia. 16mm)
Drain connecter