Table Of Contents
2. Min. length of connection pipe is 3m.
3. Max. length of connection pipe.
Max. length of connection pipe Unit: m
1. Standard length of connection pipe
5m, 7.5m, 8m.
4. The additional refrigerant oil and refrigerant charging required after prolonging
connection pipe
After the length of connection pipe is prolonged for 10m at the basis of
standard length, you should add 5ml of refrigerant oil for each additional 5m
of connection pipe.
The calculation method of additional refrigerant charging amount (on the basis
of liquid pipe):
Basing on the length of standard pipe, add refrigerant according to the
requirement as shown in the table. The additional refrigerant charging amount
per meter is different according to the diameter of liquid pipe. See the
following sheet.
Additional refrigerant charging amount = prolonged length of liquid pipe ×
additional refrigerant charging amount per meter
Configuration of connection pipe
15 25
15 30
15 30
20 30
25 30
Cooling
capacity
Max. length Max. length
of connec-
tion pipe
Cooling
capacity
of connec-
tion pipe
5000Btu/h
(1465W)
7000Btu/h
(2051W)
9000Btu/h
(2637W)
12000Btu/h
(3516W)
18000Btu/h
(5274W)
24000Btu/h
(7032W)
28000Btu/h
(8204W)
36000Btu/h
(10548W)
42000Btu/h
(12306W)
48000Btu/h
(14064W)
16