Hex Nut Diameter (in) Tightening Torque (ft-lbs)
1/4 10-13
3/8 25-30
1/2 36-45
5/8 50-60
If the lines are not already insulated, wrap them with insulation and tape
the insulation in place.
5
Wiring the Air Handlers to the outdoor unit
Remove the wire clip on the outdoor unit.
Connect the multi conductor wire that is run from the indoor air handler
to the associating terminals on the outdoor unit. Color coded multi-
conductor is highly recommended to ensure that the wires have been
connected correctly.
It is essential that the multiconductor is connected to the same connec-
tion port as the matching copper lines for each zone. The air handler with
copper lines in port A, must also have the multiconductor wiring connect-
ed to terminal block A.
Complete this step individually for each zone.
Installation of a Multi Zone Outdoor Unit