BMKH24M-NDG3 Owners & Installation Manual
Blueridge Owners Manual
31
Document Version: 11/2016
Copyright 2016 Alpine Home Air Products
• Once all of the copper lines are connected, vacuumed down to 500
microns, and the refrigerant is released, start the system.
• Ensure the gauges do not show any restriction
• Remove gauges once the system is operating properly.
NOTE
It is harmful to remove the gauges while the lineset is under vacu-
um. Keep the gauges connected until the vacuum is complete and
the refrigerant has been released into the lineset.
Multizone:
• Connect each zone’s copper lines one at a time. After connecting the first
set of copper lines, and the pressure test is complete, connect your mani-
fold gauges, micron gauge, and vacuum pump and evacuate the lineset.
• Once it is confirmed that the joints have a proper connection, pull a vacu-
um down to 500 microns.
• After the vacuum is complete, close manifold gauge valve(s), and open
both the service valves fully, release the refrigerant into the system, and
start the system.
• Move onto the next zone’s copper lines, connect them, and repeat steps
1-4.
Vacuuming