Multizone with Manifold Service Ports (one set of service ports for all
zones):
Vacuuming
1. Connect each zone’s copper lines.
2. Pressure test the entire system (all zones).
3. Connect manifold gauges, micron gauge, and vacuum pump and evacuate
the linesets.
4. Pull a vacuum down to 500 microns.
5. Close manifold gauge valves and open both the service valves fully, re-
leasing refridgerant into the system.
NOTE
It is harmful to remove the gauges while the lineset is under vacu-
um. Keep the gauges connected until the vacuum is complete and
the refrigerant has been released into the lineset.
7. Once all zones are complete, with refrigerant released, start the system
and check all zones for functionality.
8. Ensure the gauges do not show any rescrition.
9. Remove gauges.