BPM12 PTAC Submittal Sheet

Table Of Contents
PERFORMANCE DATA UNIT DIMENSION
INDOOR SIDE DATA
三视图(带墙套)
BPM12 12,000 BTU PTAC Heat Pump 3.5 kW /w remote control
Project Name:
Approval:
Location:
Date:
Submitted by:
Drawing #:
Reference:
Engineer:
Construction:
Submitted to:
Unit #:
Power supply
V,Hz,Ph
208-230V,1Ph,60Hz
Dimension(W*D*H) (without wall sleeve
inch
42x21x16
Code
22020330000061
Factory model
MWIUP-12AEN1-MJ5
Sale model BPM12
Packing (W*D*H)
inch
45.1x25.2x18.9
Capacity Btu/h 12000/11800
Net/Gross weight
Kg 52.6/56.9
72/144/180
EER
Btu/w
10.5
Indoor side fan motor
Input W 1142/1124 lbs. 116/125.4
Current
A
5.0/5.4
Loading quantity 20’ /40’ /40'HQ
Pieces
Input
W
990/963
Brand
Welling
Capacity
Btu/h
10800/10500
Model
YKT-21-6-15L
COP
W/W
3.20
FLA / OUTPUT
A / Wat
0.155 / 21
Current
A
4.3/4.6
Input
37
Capacitor uF 1.0
Speed(Hi/Mi/Lo) r/min 1100/1020/930
Indoor side air flow (Hi/Mi/Lo)
m3/h
658/596/525
Air flow & Noise level
OUTDOOR SIDE DATA
Model
ASM103N11VEZ
Outdoor side fan motor
387/351/309
Indoor side noise level (Hi/Mi/Lo)
dB(A)
52/51.5/51
Indoor side air flow (Hi/Mi/Lo)
CFM
Brand GMCC Brand Welling
Type ROTARY Model
YKT-58-4-3L
Input
W
822/835
FLA / OUTPUT
A / Wat
0.41 / 58
Capacity
Btu/h
3510/3560
Input
87
Locked rotor Amp(LRA)
A
27
Speed
r/min
1580
Rated current(RLA)
A
3.90/3.52
Capacitor
uF
3.0
Thermal protector position
INTERNAL
Outdoor side noise level
dB(A)
67/65.7/65.4
Thermal protector
UP3-41/HPA -622
Air flow & Noise level
Connection wiring
12#x3
62 -90 /32 -80
Capacitor uF
35.0
Operation temperature
Refrigerant oil/oil charge ml ESTEL OIL RB68 /300
Indoor
(cooling/ heating)
17-32/0-27
18-43/-5-24
Thermostat type
Electronic Control
64 -109 /23 -76
Plug type
LCDI 6-20P
Outdoor(cooling/heating)
Application area (Cooling EPA)
sq.ft
450-500
Application area (Cooling Standard)
m
2
16-23
Design pressure
PSIG
540/300
Refrigerant type
oz
R410A/31.39ozs
Submittal Data Sheet
Air discharge angle is 40
GRI LLE
LEFT
RIGHT

Summary of content (2 pages)