BPRPAC14 Spec Sheets

ELECTRIC/ELECTRIC PACKAGED UNIT PRPAC14
Page 2
MODEL NUMBER GUIDE
PERFORMANCE
Model
Cooling
Sound
dBA
Rated AHRI
Capacity Btuh
SEER EER
Rated Sensible
Capacity Btuh
CFM
PRPAC1424 22,600
14.0 11.0
17,400 800 77
PRPAC1430 28,400 21,900 1000 79
PRPAC1436 34,000 26,100 1200
78
PRPAC1442 40,000 30,800 1400
PRPAC1448 45,500 35,000 1600 77
PRPAC1460 57,000 41,600 1800 78
*Certified in accordance with Unitary Air Conditioner Certification Program, which is based on AHRI Standard 210/240
ELECTRICAL AND PHYSICAL DATA
Model Voltage Phase Hz
Min Volts
@ 60 hz
MCA
Max
Fuse/
HACR
Breaker
Compressor
Condenser
Motor
Blower
Motor
Refrig.
Charge
(oz.)
Weight
(lbs.)
RLA LRA RLA HP RLA HP
PRPAC1424
208-230 1 60 197
14.4 20 8.6 43.5
1.0 1/6
2.8 1/3 72 367
PRPAC1430 18.2 25 10.6 47 4.1 1/2 80 379
PRPAC1436 22.7 35 15.7 72.2 4.1 1/2 87 387
PRPAC1442 27.5 40 15.9 112.3
1.7 1/4
6 3/4 108 460
PRPAC1448 28.7 45 16.9 94 6 3/4 115 461
PRPAC1460 38.9 60 26.4 152.5 7.6 1 125 503
Minor Revision Code
Major Revision Code
Voltage
ECM - Constant Torque
Tonnage:
24, 30, 36, 42, 48, 60
Premium Residential Package Unit
Unit Type
AC = Electric Electric
SEER Family
PRP AC 14 36 E P -1 APRP AC 14 36 E P -1 A