Installation Guide
Installation of Ducting for Proper Operation:
IMPORTANT
Proper installation of ducting is extremely important for optimal performance of your ventilation system. It is a basic 
requirement that the kitchen is provided with an air intake to ensure good air circulation and therefore proper operation 
of the hood.  Without this incoming air a depression could form that would reduce the efficiency of the ventilation 
system.  All CFMS are based on tests at 0.1 static pressure.  Without static pressure all CFM’s would be overstated.
• Consult with local codes for make-up air requirements
• If ducts are combined the square inch area must reflect the total square inch area of the ducts being combined.
• Do not use flexible or corrugated duct.  This type of duct will reflect airflow and reduce performance.
• Only use smooth, galvanized metal duct.
• Make the duct run as short and as straight as possible with as few turns as possible.
• Avoid sharp-angled turns. Use smooth gradual turns such as adjustable elbows or 45 degree angled turns.
• For duct runs over 20 feet increase the duct diameter by one inch for every ten feet of duct. 
• Airflow must not be restricted at the end of the duct run.
• Damper is not provided.  This must be included in duct run to prevent back drafts.
• Do not terminate venting into an attic or chimney.
INSTALLATION INSTRUCTIONS
Ventilation Hood Mounting Instructions:
Step 1: Read all instructions thoroughly before beginning installation.  If a duct cover is being used please 
proceed to page 13.  For instructions on installing Manhattan style wall hoods proceed to page 15.
Electrical Specifications:
IMPORTANT
This hood is designed to be plugged into a 3-
prong ANSI or Non-GFCI outlet – 120Volt, 
10amp.  Ensure the outlet is not obstructed by 
the duct run prior to installation.
To connect power to in-hood blowers insert 
molex connector(s) into the opening located on 
the side of blower motor.
7