Installation Manual Ductless Mini Split Air Conditioner CRC7000012 Ductless Mini Split Air Conditioner 12K CRC7000018 Ductless Mini Split Air Conditioner 18K CRC7000024 Ductless Mini Split Air Conditioner 24K Caution:For better user experience, please follow the recommended line-set installation method in this guide. Design may vary by model number. L’aspect peut varier selon le numéro de modèle. El diseño puede variar según el número de model.
Table of Contents IMPORTANT SAFETY INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 INSTALLATION INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Step 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IMPORTANT SAFETY INFORMATION READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE WARNING For your safety, the information in this manual must be followed to minimize the risk of fire, electric shock, or personal injury. • Use this equipment only for its intended purpose as described in this manual. • This heat pump must be properly installed in accordance with these instructions before it is used. • All wiring should be rated for the amperage value listed on the rating plate. Use only copper wiring.
Installation Instructions FOR MORE HELP, VISIT WWW.BONAIREDURANGO.COM OR CALL THE CONSUMER HELP LINE AT 877-337-3639. BEFORE YOU BEGIN Read these instructions completely and carefully. IMPORTANT – Save these instructions for • local inspector’s use. IMPORTANT – • Observe all governing codes and ordinances. • Note to installer – Be sure to leave these instructions with the Consumer. • Note to consumer – Keep these instructions for future reference.
Installation Instructions Box part Breakdown Indoor Unit Box 。 Indoor Unit x1 Extra Foam Insulation x1 Mounting Plate x1 Guard Ring x2 Installation Template x1 Remote Controller + Wall Holder x1 Battery AAA x2 Wifi Dongle x1 Drain Pipe x1 Communication Cable x1 Screw Suite x1 Black Cement x2 Filter Core x1 Hexagon Wrench x1 Outdoor Unit box Power Cable Connection to Outdoor x1 Outdoor Unit x1 Vinyl Wrap x2 Line Set x2 Condenser Anti-Vibration Pads x4 5 White Mastic Sealant White Masti
Installation Instructions MINIMUM CLEARANCES (Appearance may vary) This picture is for reference only. Your product may look different. Read your manual before installation. Attention must be paid to the pitch of drain hose more than 4in. Piping Exit Advice Rear right more than 4in. IMPORTANT NOTE: more than 4in. more than 6in. more than 4in. The default position for all piping is the right side of the indoor unit (while facing the unit).
Installation Instructions Step 1 - Installation of the Indoor Unit A. Select the Indoor location: • Do not allow any heat or steam near the unit. • Select a location where there are no obstacles in front of the unit. • Make sure that condensate drainage can be conveniently routed away. • Do not install near a doorway. • Ensure that the space around the left and right of the unit is more than 4”. The unit should be installed as high on the wall as possible but allow a minimum of 4” from the ceiling.
Installation Instructions Step 1 - Installation of the Indoor Unit (Cont.) • If not able to align all screw holes with studs, wall anchors are supplied. • Be sure that the mounting plate has been attached firmly and that applied weight is evenly distributed by each screw. (At least one screw in wall stud, others can use wall anchors.) • The piping for the indoor unit need to be routed to and from the unit in one direction: right rear. See Illustration on page 6.
Installation Instructions Step 1 - Installation of the Indoor Unit (Cont.) E. Mount Indoor Unit to Mounting Plate: • Bundle the refrigerant piping, drain piping, and wiring with tape and carefully rout the bundle through the piping hole. • With the top of the indoor unit closer to the wall, hang the indoor unit on the upper hooks of the mounting plate. Slide the unit slightly side to side to verify proper placement.
Installation Instructions Step 2 - Installation of the Outdoor Unit Select the Outdoor location: •C hoose a level place solid enough to bear the weight and vibration of the OD unit and where the operation noise will not be amplified. •C hoose a location where the hot air discharge and/or noise will not create a nuisance for neighbors. •E nsure there is sufficient space to maneuver the OD unit into place. •E nsure there is sufficient space and no obstructions for the air inlet and outlet.
Installation Instructions Step 2 - Installation of the Outdoor Unit(Cont.) A. Prepare the Outdoor Unit for Installation • Remove all packaging. • Place supplied vibration pads onto outdoor unit’s feet. • If required, attach the supplied drain elbow to the outdoor unit. Connect extension piping as needed (not supplied). (see illustration) NOTE: The drain elbow is designed with an air gap and will not sit flush to bottom of the outdoor unit. NOTE: BonAire Durango models will not use a drain elbow.
Installation Instructions Step 2 - Installation of the Outdoor Unit(Cont.) C. Install the outdoor unit D. Secure the outdoor unit • The outdoor unit should be installed at least ½ mile away from the salt water, including seacoasts and inland waterways. If the unit installed from ½ mile to 5 miles away from the salt water, including seacoasts and inland waterways, please follow the installation instruction below. • Install the outdoor unit in a place (such as near buildings etc.
Installation Instructions Step 2 - Installation of the Outdoor Unit (Cont.) E. Connecting the refrigerant lineset to outdoor and indoor unit For your safety, always wear goggles and work gloves when connecting the pipes. &$87,21 %H H[WUHPHO\ FDUHIXO QRW WR NLQN RU GDPDJH WKH FRSSHU piping while unrolling the line set. Any kinks in the piping will affect the unit's performance. • ,I \RX DUH QRW FRQILGHQW DERXW FRQQHFWLQJ WKH UHIULJHDQW OLQH \RXUVHOI LW LV imperative WKDW \RX FRQWDFW RXU FXVWRPHU VHUYL
Installation Instructions Step 2 - Installation of the Outdoor Unit (Cont.) ATTENTION: Once you have made the connections from the line set to the indoor head, ensure that the black lines on the fittings are aligned. If they are not you must re tighten them until they are aligned. 3. Remove the cover on the top valve using an adjustable wrench. Using a 5mm Allen key, place key inside of the valve and turn counter clockwise slowly until you reach a stop(see figure 2).
Installation Instructions Step 2 - Installation of the Outdoor Unit (Cont.) 6. After confirming that there is no leakage in the system, use the black cement and white heat insulation pipe in the accessory to wrap the connection between the indoor unit line set connector. • Use the black cement wrap the connection part of the line set. Cut the foam insulation of suitable length, and wrap the exposed copper tube. G. Flared connection method(Requires certified HVAC Technician) 1.
Installation Instructions Step 2 - Installation of the Outdoor Unit (Cont.) This accessory is Sound Deadening Wrap. Please follow the installation instructions below. IMPORTANT If your pre-selected installation position is inconsistent with the default position in the installation operation manual, be sure to wrap the exposed lineset part of the room with this installation accessory for better user experience. This step should be applied after finishing Installation Manual Page 15 step No.6.
Installation Instructions Step 2 - Installation of the Outdoor Unit (Cont.) Manifold Gauges 2.Leak Test • Remove the cap on the service valve. • Using a tank of dry nitrogen and approved regulator, charge the system with 150 psig of dry nitrogen using mini split adapter to connect the valve. • Check for leaks at the flare fittings using soap bubbles or another detection device. If a leak is detected, make repairs to the fittings and recheck. If no leaks are detected within 3 minutes, proceed.
Installation Instructions Step 2 - Installation of the Outdoor Unit (Cont.) Contains fluorinated greenhouse gases covered by the Kyoto Protocol R410A 1= oz 2 2= oz 1+2= oz 1 F 5.
IMPORTANT If you have a problem with this product, Visit our website at www.bonairedurango.com For Technical Advice/Warranties call 800-939-2983 or mail us at info@bonairedurango.com Monday to Friday 8:00 A.M. – 1:00 P.M.