Operating instructions
154  Application manual Positioning  04/08
6.3 Status word 411 
Parameter 
Status word 411 includes two specific bits of the positioning. These bits 
can be evaluated by the logic control. 
 Note: 
The applicable status word is dependent on the operation mode 
Lo-
cal/Remote
 412. The status word is used in most of the operation modes 
for parameter 
Local/Remote 412. 
If the inverter is controlled via statemachine (
Local/Remote  412 = „1 - 
Control via Statemachine“) a different status word is applicable. Refer to 
the operating instructions of the communication modules or expansion 
modules. 
Statusword 411 
Bit-No.  Function 
0  Ready for being switched on   
1  Switched on   
2  Operation – released   
3 Error   
4  Voltage – disabled   
5  Quick Stop   
6  Starting lock-out   
7 Warning   
 8 Homing Done   
9 Remote   
10  Reference value reached   
11  Limit value reached   
12 -   
13 -   
14  Target Position Reached   
15  Warning 2   
  8  Homing Done. 
Homing is carried out successfully. The home position is set. This bit 
stays set until homing is restarted. 
The bit is only output in the settings of parameter 
Local/Remote 412 ≠ 
“1 - Control via Statemachine”. 
  14  Target Position Reached. 
Target Position/Distance
1202 of a positioning operation was reached, 
and current actual position is within the range set in parameter 
Target 
window
1165 for a minimum period of Target window time 1166. 
The bit is only output in the settings of parameter 
Local/Remote 412 ≠ 
“1 - Control via Statemachine”. 
The bit is reset if: 
−
The drive travels out of the range set in parameter 
Target window
1165 or 
− JOG-Mode is enabled or 
− Homing is started or 
− Operation mode “Teach-In” is enabled 
Application manual Positioning 04/08154