Operating instructions
1311/06
11/06 13
4.4 Baud rate setting/line length 
The setting of the baud rate must be identical in all nodes on the system bus. The
maximum possible baud rate is based on the necessary overall line length of the sys-
tem bus. The baud rate is set via the parameter 
Baud-Rate 903 and thus defines the 
possible line length. 
Operation mode  Function max. line length 
3 - 50 kBaud  Transmission rate 50 kBaud  1000 meters 
4 - 100 kBaud  Transmission rate 100 kBaud  800 meters 
5 - 125 kBaud  Transmission rate 125 kBaud  500 meters 
6 - 250 kBaud  Transmission rate 250 kBaud  250 meters 
7 - 500 kBaud  Transmission rate 500 kBaud  100 meters 
8 - 1000 kBaud  Transmission rate 1000 kBaud  25 meters 
A baud rate under 50 kBaud, as is defined according to CANopen, is not sensible for
the system bus as the data throughput is too low. 
The maximum line lengths stated are guidelines. If they are made complete use of, a 
calculation of the admissible length is to be done on the basis of the line parameters 
and the bus driver (PCA82C250T). 
4.5 Setting node address 
A maximum of 63 slaves or frequency inverters with system bus can be operated on
the system bus. Each frequency inverter is given a node ID, which may only exist
once in the system, for its unambiguous identification. The setting of the system bus
node ID is done via the parameter 
Node-ID 900.
Parameter Setting
No.  Description  min.  max.  Factory setting 
 900 Node-ID  -1 63  -1 
Thus, the system bus possesses a maximum number of 63 nodes (Network nodes),
plus one frequency inverter as a master. 
Note:
With the factory setting of parameter 
Node-ID 900 = -1, the system bus 
is deactivated for this frequency inverter. 
If the 
Node-ID 900 = 0 is set, the frequency inverter is defined as a mas-
ter. Only one frequency inverter on the system bus may be defined as a
master.










