Technical data
32
CANopen / CM-CAN 
communication
The CM-CAN communication option with controller area network interface, complies 
with ISO/DIS 11898 transmission standard. The pinout of connector DB9 is based on 
the “CAN in Automation e.V.” specification, which allows the connection of up to 127 
nodes in the network. The network node addresses are assigned via software. The 
endburden resistor is activated by means of a DIP switch on the module. The end of 
line terminating current transmission protocol complies with CANopen specifications 
DS-301 V4.02. The maximum allowed distance between the bus nodes depends on the 
cable used and the selected transmission rate. See table.
Cable lenght Max Baud rate
up to 5000m 10
up to 2500m 20
up to 1000m 50
up to 800m 100
up to 500m 125
up to 250m 250
up to 100m 500
up to 25m 1000
Cable length limits the transmission 
bandwith. Above table shows the match 
between admissible cable lengths and 
corresponding max kBaud rates. Values are 
indicative and may significantly change 
in relation to the transmission cable 
characteristics.