4.1.7  Error and warning behavior 
  The monitoring of the analog input signal necessary accordin
g
 to the application is to
be configured via the parameter 
Error/Warning behavior 563. 
  Operation mode  Function 
  0 - Off  The input signal is not monitored. 
1 - Warning < 1 V / 2 mA 
If the input signal is less than 1 V or 2 mA, there 
is a warning message. 
2 - Shutdown < 1 V / 2 mA 
If the input signal is less than 1 V or 2 mA, there 
is a warning message, the drive mechanism is 
decelerated according to stopping behavior 1. 
3 -
Fault switch-off 
< 1 V / 2 mA 
If the input signal is less than 1 V or 2 mA, there 
is a warning and fault message and the drive 
mechanism stops freely. 
T
he monitorin
g
 of the analo
g
 input si
g
nal is active independent of the release of the
frequency inverter according to the operation mode selected. 
 In operation mode 2, the drive mechanism is decelerated independent of the stoppin
g
behavior set (Parameter Operation mode  630) accordin
g
 to stoppin
g
 behavior 1
(shutdown and switch-off). If the set holding time has expired, there is a fault mes-
sage. A repeat start of the drive mechanism is possible by switchin
g
 the start si
g
nal on
and off if the fault has been cleared. 
 Operation mode 3 defines the free stoppa
g
e of the drive mechanism, independent o
f
the stopping behavior selected, which is stipulated with the parameter Stop function
630. 
  Attention! 
Monitoring of the analog input signal via the parameter 
E
rror/Warnin
g
Behavior
 563 demands a check of the characteristic parameters. 