Operating instructions
08/06    17
4.1.8  Adjustment 
  As a result of component tolerances, it can be necessary to ad
j
ust the analo
g
 input. 
Parameter 
Adjustment 568 is used for this purpose. 
  Operation mode  Function 
  0 - no adjustment  Normal operation 
1 - Adjustment 0 V / 0 mA 
Adjustment of the measurement with an analog 
signal of 0 V or 0 mA. 
2 - Adjustment 10 V / 20 mA 
Adjustment of the measurement with an analog 
signal of 10 V or 20 mA. 
  Example of the adjustment of the analog input with a voltage signal: 
  Note: 
T
he measurements for the ad
j
ustment are to be done with a suitable
measuring instrument and the correct polarity. 
If not, faulty measurements can result. 
  •  Apply 0 V to the analo
g
 input; e.
g
. with a wired link from the socket of the analo
g
input X410B.4 to socket X210B.7 (earth/GND) of the frequency inverter. 
  •  Select operation mode "1 - Adjustment 0 V / 0 mA“. 
  •  Apply 10 V to the analog input, e.g. with a wired link from the socket of the ana-
log input to socket X210B.5 (reference output 10 V) of the frequency inverter. 
  •  Select operation mode "2 - Adjustment 10 V / 20 mA“. 
4.1.9  Filter time constant 
  The time constant of the filter for the reference analog value can be set via the pa-
rameter 
Filter time constant 561. 
T
he time constant states the time for which the input si
g
nal is avera
g
ed by means of a
low pass filter, e.g. in order to eliminate fault effects. 
  The setting range is a range of values between 0 ms and 5000 ms in 15 steps. 
  Operation mode  Function 
0 - Time constant 0 ms 
Filter deactivated – analog reference value is for-
warded unfiltered 
  2 - Time constant 2 ms 
  4 - Time constant 4 ms 
  8 - Time constant 8 ms 
  16 - Time constant 16 ms 
  32 - Time constant 32 ms 
  64 - Time constant 64 ms 
  128 - Time constant 128 ms 
  256 - Time constant 256 ms 
  512 - Time constant 512 ms 
  1000 - Time constant 1000 ms 
  2000 - Time constant 2000 ms 
  3000 - Time constant 3000 ms 
  4000 - Time constant 4000 ms 
  5000 - Time constant 5000 ms 
Filter activated – averaging of the input signal via 
the set value of the filter time constants 