Operating instructions
08/06    11
4  System bus interface 
  The CAN connection of the system bus is physically designed according to ISO-DIS 
11898 (CAN High Speed). The bus topology is the line structure. 
  In the default version, the frequency inverter support a CAN protocol controller, which 
may exist in either the CM-CAN communication module with CANopen interface OR in 
an expansion module for the system bus, such as the EM-RES-01 expansion module. 
  Attention!  Installation of two optional components with CAN-Protocol controller re-
sults in a deactivation of the system bus interface in the EM-RES-01 ex-
pansion module. 
4.1  Bus termination 
  The necessary bus terminator at the physically first and last subscriber can alternativel
y
be activated via the two DIP switches S1 and S2 on the EM-RES-01 expansion mod-
ule. 
•  Either set S1 to ON and S2 to OFF for a passive termination, 
•  or set S1 and S2 to ON for an active termination. This results in an improved ed
g
e 
shape of the CAN signals, which results in an improvement of the signal shapes, in 
particular in extended systems. 
  Note:  Switch S3 is used to confi
g
ure the analo
g
 input (see chapter "Analo
g
 inpu
t
EM-S1INA“). 
X410A
X
410B
S1
S2
S3
  Attention!  The factory setting for the bus termination is OFF. 
An active termination may only be switched once on a bus system via S1
and S2. The other bus termination has to be done in passive mode. 
CAN  high (X410B.6)
120 
Ω
CAN  low (X410B.5)
Data line
Data line
CAN  high (X410B.6)
332 
Ω
CAN low (X410B.5)
Data line
Data line
passive active
332 
Ω